Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
Solutions Ex d IIB or CID1 / CIID1 based on Aluminum Enclosures |
Electrical specifications | ||
---|---|---|
Operating voltage | 1500 V DC / 1000 V AC max. for ATEX / IECEx 600 V AC / DC max. for North American approvals |
|
Operating current | 1600 A max. | |
Mechanical specifications | ||
Thread type | metric ISO pitch 1.5 mm or NPT ANSI ASME B1.20.1 | |
Enclosure cover | detachable , optional hinges | |
Cover fixing | stainless steel socket cap head screws | |
Screws | see data table | |
Material of screws | stainless steel | |
Yield stress | min. 450 N/mm2 for ATEX / IECEx , 100,000 PSI for North American approvals | |
Cover seal | none, O-ring for IP66/67 | |
Flamepath grease | Greasil MS4 or NEVER SEEZ Marine Grade | |
Degree of protection | IP66 (IP66/67 with O-ring) , NEMA Type 4, 4X, 7, 9 | |
Cable entry | see data table | |
Material | ||
Enclosure | aluminum alloy | |
Glass | thermo-resistant tempered glass | |
Finish | epoxy coated RAL 7005 (grey) | |
O-Ring | silicone | |
Mass | see data table valid for empty enclosure, will increase according to integrated components |
|
Dimensions | see data table values might differ slightly due to casting and manufacturing tolerances dimensions are valid for standard enclosures and IP66 variants only |
|
Mounting | see data table | |
Grounding | M6 external grounding points | |
Ambient conditions | ||
Ambient temperature | -50 ... 60 °C (-58 ... 140 °F) depending on integrated components |
|
Data for application in connection with hazardous areas | ||
EU-type examination certificate | INERIS 14 ATEX 0022X INERIS 14 ATEX 9010U |
|
Marking | II 2 GD Ex db IIB+H2 T* Gb Ex tb IIIC T** °C Db T6/T85 °C T5/T100 °C T4/T135 °C T3/T200 °C depending on configuration, ambient temperature and built-in power loss |
|
Maximum power dissipation | see data table maximum power dissipation at T4/+40 °C enclosure without window |
|
International approvals | ||
UL approval | ||
Approved for | Class I, Division 1, Groups B, C, D Class II, Division 1, Groups E, F, G Type 4, 4X, 7, 9 |
|
cULus | Empty enclosure E482035 , UL 50E , UL 1203 , CSA C22.2, No. 25, 30 | |
cETLus | Control panels E5003368 | |
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) | |
IECEx approval | IECEx INE 14.0029X IECEx INE 14.0028U |
|
UKCA approval | CML 21 UKEX 1424X CML 21 UKEX 1425U |
|
ECAS approval | 22-09-51655/E22-09-051712/NB0002 | |
CCC approval | 2020322303002546 | |
Further approvals | available on request | |
Conformity | ||
Degree of protection | EN60529 and UL 50 / UL 50E | |
CE marking | 0080 or 0102, see type label | |
General information | ||
Ordering information | This solution will be delivered completely configured and assembled ready for use. For configuration details please contact Customer Service. | |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27180502 |
ECLASS 12.0 | 27180502 |
ECLASS 11.0 | 27180502 |
ECLASS 10.0.1 | 27180502 |
ECLASS 9.0 | 27180502 |
ECLASS 8.0 | 27149144 |
ECLASS 5.1 | 27180502 |
ETIM 9.0 | EC002503 |
ETIM 8.0 | EC002503 |
ETIM 7.0 | EC002503 |
ETIM 6.0 | EC002503 |
ETIM 5.0 | EC002713 |
UNSPSC 12.1 | 39121314 |
The enclosure series EJB forms the optimal basis for the application-specific configuration of terminal boxes, control stations as well as control and distribution panels.
The enclosures are certified Ex d IIB+H2 and Ex tb as well as "explosion-proof". They are available in many sizes, a wide range of operating elements and monitoring functions can be integrated. They are manufactured from copper-free aluminum with increased corrosion resistance.
This durability as well as the flexible customization options cover the requirements of many industries including offshore and marine applications. A choice of windows allows viewing of integrated monitoring functions. Electrical components can be integrated as per customer specification.
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
||||
---|---|---|---|---|---|---|---|---|---|---|---|
EJB |
* |
** |
. |
** |
. |
* |
. |
** |
- |
* |
**** |
EJB |
17Q |
. |
W1 |
. |
D |
. |
CP |
- |
Y |
0001 |
Example: EJB17Q.W1.D.CP-Y0001
Control panel EJB size 17Q in aluminum, rectangular window type 1, without intrinsically safe circuits
1 |
Enclosure type |
---|---|
EJB |
enclosure Ex d IIB+H 2 |
2 |
Material |
---|---|
copper-free aluminum |
3 |
Enclosure size |
---|---|
0 ... 20A |
see dimensions data table |
4 |
Window |
---|---|
no window |
|
W ... |
rectangular window with type indication |
WG ... |
circular window with type indication |
5 |
Electrical circuits |
---|---|
D |
without intrinsically safe circuits |
I |
intrinsically safe circuits integrated |
6 |
Type of application |
---|---|
U |
empty enclosure |
T |
terminal box ATEX / IECEx |
TD1 |
terminal box UL Class 1, Division 1 / Class 2, Division 1 |
CP |
control panel ATEX / IECEx |
CPD1 |
control panel UL Class 1, Division 1 / Class 2, Division 1 |
CS |
control station ATEX / IECEx |
CSD1 |
control station UL Class 1, Division 1 / Class 2, Division 1 |
DB |
distribution board |
DMT |
electronic earthing system |
MS |
motor starter |
PS |
power switching |
RIO |
remote I/O field unit |
IFS |
interface solution |
FJB |
fieldbus solution |
OS |
optical solution |
Q40 |
engineered solution per customer specification (Q40) |
7 |
Variant |
---|---|
S |
standard product |
C |
configured Product |
Y |
engineered Product |
8 |
Variant number |
---|---|
xxxx |
consecutive number |
Brief Instructions | Language | File Type | File Size |
---|---|---|---|
Instruction Manual EJB | ENG | 256 KB |
Certificates | Cert No. | Language | File Type | File Size |
---|---|---|---|---|
China SITIIAS CCC Ex Certificate | 2020322303002546 (Pepperl+Fuchs SE,Mannheim) | ALL | 2867 KB | |
Europe INERIS ATEX | INERIS 14 ATEX 0022X | ALL | 543 KB | |
INERIS IECEx Certificate of Conformity | IECEx INE 14.0029X | ALL | LINK | --- |
INERIS IECEx Certificate of Conformity | IECEx INE 14.0028U | ALL | LINK | --- |
UK-Type Examination Certificate | CML 21UKEX1424X | ALL | 148 KB | |
UK-Type Examination Certificate | CML 21UKEX1425U | ALL | 220 KB | |
UL Hazardous Location | E482035 (FTRV) | ALL | 400 KB | |
Control Drawings | ||||
Control drawing UL / Control drawing UL | ALL | 182 KB | ||
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2468E | ALL | 446 KB | |
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-0832G | ALL | 387 KB |