General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Rated voltage | loop powered | |
Power dissipation | < 1 W | |
Input | ||
Connection side | control side | |
Connection | terminals 5, 6 | |
Rated voltage | 19 ... 30 V DC | |
Current | ≤ 72 mA at Ui = 19 V, ≤ 50 mA at Ui = 30 V with 265 Ω output load ≤ 45 mA at Ui = 19 V, ≤ 31 mA at Ui = 30 V with shorted output ≤ 14 mA at Ui = 19 V, ≤ 11 mA at Ui = 30 V no load at output |
|
Inrush current | ≤ 200 mA after 100 µs | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Internal resistor | ≤ 238 Ω | |
Current | ≤ 45 mA | |
Voltage | ≥ 12 V | |
Open loop voltage | ≥ 22.7 V | |
Output current | 45 mA | |
Output signal | These values are valid for the rated operating voltage 19 ... 30 V DC. | |
Energized/De-energized delay | single operation: typ. 1.7 ms/50 µs; periodical: typ. 5 µs/50 µs | |
Galvanic isolation | ||
Input/Output | reinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LED | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Protection against electrical shock | UL 61010-1 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2 | |
Height | 119 mm | |
Width | 12.5 mm | |
Depth | 114 mm | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | BASEEFA 06 ATEX 0170 | |
Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I | |
Output | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
Voltage | 25.2 V | |
Current | 110 mA | |
Power | 693 mW | |
Input | ||
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
Certificate | PF 06 CERT 0971 X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0419 (cFMus) | |
UL approval | ||
Control drawing | 116-0420 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx BAS 06.0032 | |
IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210101 |
ECLASS 12.0 | 27210190 |
ECLASS 11.0 | 27210190 |
ECLASS 10.0.1 | 27210190 |
ECLASS 9.0 | 27210190 |
ECLASS 8.0 | 27210190 |
ECLASS 5.1 | 27210121 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 39121008 |
This isolated barrier is used for intrinsic safety applications.
The device supplies power to solenoids, LEDs and audible alarms located in a hazardous area.
The device is loop powered, so the available energy at the output is received from the input signal. The output signal has a resistive characteristic. As a result the output voltage and current are dependent on the load and the input voltage
At full load, 12 V at 45 mA is available for the hazardous area application.
Literature | Language | File Type | File Size |
---|---|---|---|
Application Report - Energy Generation in Wastwater Treatment Plants | ENG | 532 KB | |
Application Report - Generating Electricity in Coal-Fired Power Plants | ENG | 412 KB | |
Application Report - Screening Systems in Sewage Treatment Plants | ENG | 577 KB | |
Application Report - Sicherer Brennstofftransport in Kohlekraftwerken | ENG | 391 KB | |
Application Report - Water Inlet in Wastewater Treatment Plants | ENG | 526 KB |
Product information | Language | File Type | File Size |
---|---|---|---|
Application Guideline Solenoid Drivers | ENG | 734 KB | |
Safety and Security Documentation | |||
Instruction manual | ENG | 168 KB | |
Safety Manual | ENG | 414 KB | |
Manuals | |||
Manual | ENG | 3685 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 3086 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
EPLAN macro EDZ / EPLAN Makro EDZ | ALL | EDZ | 42 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
Australia SIMTARS Group I | ANZEx 08.2007X | ALL | 295 KB | |
Baseefa IECEx Certificate of Conformity | IECEx BAS 06.0032 | ALL | LINK | --- |
Canada FM | FM18CA0116X | ALL | 2690 KB | |
Canada UL cUL | E106378 cUL (QUZW7) | ALL | LINK | --- |
China SITIIAS CCC Ex Certificate | 2020322316001222 (Singapore) | ALL | 1036 KB | |
DNV Marine | TAA00001WX | ALL | 114 KB | |
Europe Baseefa ATEX Category (M1) ATEX Category (1) GD | Baseefa 06 ATEX 0170 | ALL | 679 KB | |
Europe Pepperl+Fuchs ATEX Category 3 G | PF06CERT0971X | ALL | 195 KB | |
India PESO (India) CCOE | A/P/HQ/KA/104/6090 (P577495) | ALL | 125 KB | |
Korea KOSHA [Ex ia] | 17-AV4BO-0294 | ALL | 457 KB | |
South Africa MASC | MASC MS/17-0857 | ALL | 216 KB | |
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378 | CoC 20170501 - E106378 RepRef 20081022 | ALL | 244 KB | |
USA FM | FM19US0117X | ALL | 2447 KB | |
USA UL | E106378 UL (QUZW) | ALL | LINK | --- |
exida Functional Safety Assessment | P+F 1109-099-C R028 V1R0 | ALL | 380 KB | |
Control Drawings | ||||
Control drawing UL / Control drawing UL | ALL | 209 KB | ||
Control drawing FM / Control drawing FM | ALL | 208 KB | ||
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-0026B | ALL | 54 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||