Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

AS-Interface sensor/actuator module VBA-4E4A-G11-ZAJ/EA2L-F

  • Inputs for 2-, 3-, and 4-wire sensors
  • Power supply of outputs from the external auxiliary voltage
  • Supply of sensors from AS-Interface
  • Function display for bus, external auxiliary voltage, in- and outputs
  • Red LED per channel, lights up in the event of output overload
  • Communication monitoring
  • Switchable lead breakage detection (outputs)
  • Cable piercing method with gold plated contact pins
  • Degree of protection IP68 / IP69K
  • AS-Interface POWER24

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of VBA-4E4A-G11-ZAJ/EA2L-F

Product Description
G11 module
4 inputs and 4 outputs
General specifications
Slave typeA/B slave
AS-Interface specificationV3.0
Required master specification≥ V3.0
UL File NumberE223772
Functional safety related parameters
MTTFd120 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Indicators/operating means
LED AS-i/FAULTStatus display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: sensor supply i.e. overload or lead interruption outputs
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INswitching state (input); 4 LED yellow
LED OUTswitching state (output); 4 LED yellow/red
yellow: output active
red: output overload or lead interruption
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage18,0 ... 31.6 V from AS-Interface
Rated operating current≤ 40 mA (without sensors) / max. 240 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
option 2 inputs for 4-wire sensors (PNP), DC
Supplyfrom AS-Interface
Voltage12 ... 31 V
Current loading capacity≤ 200 mA, overload and short-circuit protected
Input current≤ 9 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 3 mA
1 (attenuated)≥ 5 mA
Signal delay< 1 ms (input/AS-Interface)
Output
Number/Type4 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Current2 A per output
TB ≤ 40 °C: 6 A total
TB ≤ 70 °C: sum O1 + O2 max. 2 A, sum O3 + O4 max. 2 A
Voltage≥ (UAUX - 0.5 V)
Electrical isolation
Input/Outputsafe isolation, rated insulation voltage 40 V DC
Output/AS-Interfacesafe isolation, rated insulation voltage 40 V DC
Compliance with standards and directives
Directive conformity
EMC Directive 2004/108/ECEN 61000-6-2:2005, EN 61000-6-4:2007, EN 50295:1999
Standard conformity
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 50295:1999
Emitted interferenceEN 61000-6-4:2007
InputEN 61131-2:2007
Degree of protectionEN 60529:2000
Fieldbus standardEN 50295:1999, IEC 62026-2:2006
Programming instructions
ProfileS-7.A.7
IO code7
ID codeA
ID1 code7
ID2 code7
Data bits (function via AS-Interface) input output
D0 IN1 O1
D1 IN2 O2
D2 IN3 O3
D3 IN4 O4
Parameter bits (programmable via AS-i)function
P0Communication monitoring
P0 = 0 monitoring = off, the outputs maintain the status if communication fails
P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
P1Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
P2Lead breakage outputs
P2 = 0 lead breakage on
P2 = 1 lead breakage off (default settings)
P3not used
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree3
Mechanical specifications
Degree of protectionIP68 / IP69K
ConnectionAS-Interface/UAUX: AS-Interface flat cable
Inputs/outputs: M12 round connector
Material
HousingPBT PC
Mounting screwStainless steel 1.4305 / AISI 303
Mass200 g
Tightening torque, housing screws1.8 Nm
Tightening torque, cable gland0.4 Nm
MountingMounting plate

Documents: VBA-4E4A-G11-ZAJ/EA2L-F

Instruction leafletsLanguageFile TypeFile Size
Instruction leaflet / BeipackzettelALLPDF1536 KB

CAD+CAE: VBA-4E4A-G11-ZAJ/EA2L-F

CADFile TypeFile Size
3-D model in IGS format / 3-D-Modell im IGS-FormatIGS6099 KB
3-D model in STP format / 3-D-Modell im STP-FormatSTP4756 KB

Approvals+Certificates: VBA-4E4A-G11-ZAJ/EA2L-F

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0991APDF162 KB
Certificates
US CA ULE223772LINK---
Worldwide AS-International Association AS-Interface89701PDF603 KB
EU Ecolab Material ResistanceECOLABPDF1797 KB

Associated Products: VBA-4E4A-G11-ZAJ/EA2L-F

AccessoriesName
VAZ-V1-B3Blind plug
VBP-HH1-V3.0-KITAS-Interface Handheld with accessory
VAZ-PK-1,5M-V1-GAdapter cable module/hand-held programming device
VAZ-FK-S-BK-SEALAS-Interface seal

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Download the AS-Interface Product Overview

Get to know our full range of AS-Interface products.