| General specifications |
| Type | DC version, positive polarity |
| Electrical specifications |
| Nominal resistance | 150 Ω |
| Series resistance | max. 166 Ω |
| Fuse rating | 50 mA |
| Hazardous area connection |
| Connection | terminals 1, 2 |
| Safe area connection |
| Connection | terminals 7, 8 |
| Rated voltage | 22 V |
| Supply voltage | max. 20.1 V |
| Working voltage | 19 V at 10 µA |
| Conformity |
| Protection degree | IEC 60529 |
| Ambient conditions |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
| Protection degree | IP20 |
| Connection | self-opening connection terminals, max. core cross-section 2 x 2.5 mm2 |
| Mass | approx. 150 g |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 in) |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Data for application in connection with Ex-areas |
| EC-Type Examination Certificate | BAS 01 ATEX 7005 , for additional certificates see www.pepperl-fuchs.com |
| Group, category, type of protection | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2] |
| Statement of conformity | TÜV 99 ATEX 1484 X , observe statement of conformity |
| Group, category, type of protection, temperature class | II 3G Ex nA IIC T4 Gc [device in zone 2] |
| Directive conformity | |
| Directive 94/9/EC | EN 60079-0:2009, EN 60079-11:2007, EN 61241-11:2006 , EN 60079-15:2010 |
| International approvals |
| FM approval | |
| Control drawing | 116-0118 |
| UL approval | |
| Control drawing | 116-0139 |
| CSA approval | |
| Control drawing | 116-0119 |
| IECEx approval | IECEx BAS 09.0142
|
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |