| General specifications |
| Type | AC version |
| Electrical specifications |
| Nominal resistance | without back-up fuse 792 Ω , with back-up fuse 795 Ω |
| Series resistance | without back-up fuse max. 801 Ω , with back-up fuse max. 804 Ω |
| Fuse rating | internal fuse 160 mA , back-up fuse 125 mA |
| Hazardous area connection |
| Connection | terminals 13; 23 |
| Safe area connection |
| Connection | terminals 11; 21 |
| Working voltage | 2.5 V at 2 µA |
| Conformity |
| Protection degree | IEC 60529 |
| Ambient conditions |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Storage temperature | -40 ... 80 °C (-40 ... 176 °F) |
| Mechanical specifications |
| Protection degree | IP20 (installed on Terminal Base or Termination Board) |
| Connection | wiring via Terminal Base or Termination Board |
| Mass | approx. 70 g |
| Dimensions | 9.7 x 70.4 x 68.2 mm (0.4 x 2.8 x 2.7 in) |
| Mounting | Terminal Base or Termination Board mounting on 35 mm DIN rail acc. to DIN EN 60715 |
| Data for application in connection with Ex-areas |
| EC-Type Examination Certificate | TÜV 99 ATEX 1449 X , for additional certificates see www.pepperl-fuchs.com |
| Group, category, type of protection | II (1) G [Ex ia] IIC
II (1) D [Ex iaD] |
| Directive conformity | |
| Directive 94/9/EC | EN 60079-0:2009, EN 60079-11:2012, EN 60079-26:2007 |
| International approvals |
| UL approval | |
| Control drawing | 16-557UL-12 (cUL) |