Serviceline Industrial Sensors
Serviceline Explosion Protection

Fieldbus Power Hub, Power Supply Module HD2-FBPS-1.25.360

HD2-FBPS-1.25.360
  • 2 segments, simplex, individual modules per segment
  • Couples PROFIBUS PA devices transparently to PROFIBUS DP
  • High-power trunk: Live work on devices in any hazardous area
  • Transparent, configuration free
  • Optimized for size and quality, low heat dissipation
  • Automatically adapts speed on DP - up to 12 Mbit/s
  • Output: 25 ... 28 V/360 mA
  • Universal power supply for most applications
  • With galvanic isolation
  • Installation in Zone 2/Class I, Div. 2
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • High efficiency, low heat dissipation for high packing density
  • Hot swappable in redundant configuration
  • Module exchange without tools during operation

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HD2-FBPS-1.25.360

Product Description
2-channel power supply system, modular, motherboard-based with transparent coupling between PROFIBUS DP and PA. motherboard and modules
General specifications
Design / MountingMotherboard based
Supply
Rated voltage19.2 ... 35 V DC
Rated current670 ... 360 mA
Power dissipationtyp. 2 W
Fieldbus connection
Rated voltage25 ... 28 V
Rated current360 ... 10 mA
Short-circuit currenttyp. 400 mA
Indicators/operating means
LED ERRred flashing: overload error at output
LED PWRPower LED: green if Uout > 25 V
Galvanic isolation
Fieldbus segment/Supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typemotherboard specific
Core cross sectionmotherboard specific
Housing materialPolycarbonate
Degree of protectionIP20
Massapprox. 150 g
Dimensions
Height106 mm
Width18 mm
Depth128 mm
Mountingmotherboard mounting
Data for application in connection with hazardous areas
CertificateTÜV 06 ATEX 553229 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
FM certificateFM 19 US 0015 X and FM 19 CA 0011 X
FM markingAEx/Ex ec IIC T4
IECEx approval
IECEx certificateIECEx TUN 11.0003X
IECEx markingEx nA IIC T4 Gc
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242611
ECLASS 12.027242611
ECLASS 11.027242611
ECLASS 10.0.127242611
ECLASS 9.027242611
ECLASS 8.027242611
ECLASS 5.127242611
ETIM 9.0EC002583
ETIM 8.0EC002583
ETIM 7.0EC002583
ETIM 6.0EC002583
ETIM 5.0EC001604
UNSPSC 12.139121004

Details: HD2-FBPS-1.25.360

Function

This Power Supply Module is a system component for the FieldConnex ® Power Hub and can be plugged into the motherboard. It adapts current and voltage for the supply of fieldbus segments and field devices.

This power supply satisfies the needs of most fieldbus applications with regards to cable lengths and number of devices.

Reliability of communication is enhanced through galvanic isolation between segment and bulk power supply. Two LEDs indicate power and status. In redundant configuration two modules are connected in parallel via simple circuits ensuring seamless operation.

Informative Literature: HD2-FBPS-1.25.360

Language Selection:
LiteratureLanguageFile TypeFile Size
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB
Application Report - Fieldbus Power Supply Compatible with Process Industry ApplicationsENGPDF229 KB

Product Documentation: HD2-FBPS-1.25.360

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Instruction manualENGPDF230 KB

Approvals: HD2-FBPS-1.25.360

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
Canada FMFM 19 CA 0011XALLPDF356 KB
DNV MarineTAA0000272ALLPDF100 KB
Europe TUV Nord ATEX Category 3 GTÜV 06 ATEX 553229XALLPDF2610 KB
USA FMFM 19 US 0015XALLPDF213 KB
Worldwide Fieldbus FoundationPS002500ALLPDF166 KB
Worldwide TUV Nord IECEx nAIECEx TUN 11.0003XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-2264BENGENGPDF1140 KB

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

From decisions to planning, installation, and commissioning up to operation and maintenance: Discover how to make the most out of your fieldbus infrastructure …