PROFINET Power Hub, Gateway Module HD2-GTR-4PA.PN

HD2-GTR-4PA.PN
  • Gateway PROFINET RT to 4 x PROFIBUS PA segments
  • Up to 32 devices per PROFIBUS PA segment
  • Installation in Zone 2/Class I, Div. 2
  • Ring and system redundancy
  • Integrated webserver for diagnostics

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  HD2-GTR-4PA.PN

General specifications
Design / MountingMotherboard based
Supply
Rated voltage19.2 ... 35 V SELV/PELV
Rated currenttyp. 135 mA
Power dissipationapprox. 3.5 W
Fieldbus connection
Number of segments4
Number of devices per segmentmax. 32
Fieldbus typePROFIBUS PA
Ethernet Interface
Number of ports2
ProtocolPROFINET
Ethernet InterfaceConnector plug , 2x RJ45
Transfer rate100 MBit/s
RedundancyRing (MRP) , System S2
Indicators/operating means
LED ETH1 LINK 2green: link status
LED ETH1 ACTyellow: activity status
LED ETH2 LINKgreen: link status
LED ETH2 ACTyellow: activity status
LED ERRred 2 Hz flashing: Ethernet error
LED Seg 1...4red 2 Hz flashing: PA error, red and LED DP/ERR red: MAU error
LED PWRgreen: Power on
LED DP/ERRred 2 Hz flashing: DP error ; red: Hardware error
LED Red.yellow: redundant operation primary device ; yellow 2 Hz flashing: synchronization or redundancy not available
Galvanic isolation
CH/PROFIBUS DPfunctional insulation acc. to IEC 61010, rated insulation voltage 50 Veff
PROFIBUS DP/Supplyfunctional insulation acc. to IEC 61010, rated insulation voltage 50 Veff
CH/CHfunctional insulation acc. to IEC 61010, rated insulation voltage 50 Veff
CH/Ethernetfunctional insulation acc. to IEC 61010, rated insulation voltage 50 Veff
All circuits/FEfunctional insulation acc. to IEC 61010, rated insulation voltage 50 Veff
Ethernet/Supplyfunctional insulation acc. to IEC 61010, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F) vertically mounted , -40 ... 70 °C (-40 ... 158 °F) horizontally mounted
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Housing materialPolycarbonate
Degree of protectionIP20
Mass250 g
Dimensions
Height106 mm
Width40 mm
Depth128 mm
Mountingmotherboard mounting
Data for application in connection with hazardous areas
CertificateTÜV 15 ATEX 7735 X
MarkingEx-Hexagon II 3 G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018
International approvals
IECEx approvalIECEx TUR 16.0007X
Approved forEx ec IIC T4 Gc
Certificates and approvals
Marine approvalpending
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242610
ETIM 9.0EC001600
ETIM 8.0EC001600
ETIM 7.0EC001600
ETIM 6.0EC001600
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: HD2-GTR-4PA.PN

The PROFINET to PROFIBUS PA gateway integrates communication of 4 PA segments into PROFINET I/O systems. The gateway is part of the FieldConnex ® Power Hub system. The gateway operates with power supply modules connected to the same or a separate motherboard.

The gateway provides a PA master for each segment and thus enables short bus cycle times.

One single gateway supports S2 system redundancy and ring redundancy.

A complete toolchain supports the engineering for system integration. A gateway device type manager (DTM) and a webserver enable access to both status and diagnostics of the gateway. The gateway DTM enables communication for parameterization, diagnostics, and status information to PROFIBUS PA devices through vendors’ DTMs. A library of STEP 7 software modules for integration into Siemens PCS7 is available.

The PROFINET gateway is an ideal solution for new plants and for upgrading existing PROFIBUS PA installations from PROFIBUS DP to PROFINET.

Datasheet: HD2-GTR-4PA.PN

DatasheetFile TypeFile Size
Datasheet HD2-GTR-4PA.PNPDF704 KB
Datenblatt HD2-GTR-4PA.PNPDF698 KB

Documents: HD2-GTR-4PA.PN

ManualsFile TypeFile Size
PROFINET Manual for use with HD2-FB*, MB-FB*.GEN, MBHD-FB*.GEN, MBHD-FB-D-4R.GEN, MB-FB-GT, MB-FB-GTRPDF4416 KB
Instruction manuals
ИнструкцииPDF166 KB
Instruction manual / BetriebsanleitungPDF320 KB
Návod k poużitíPDF160 KB
Instruktions manualPDF160 KB
Instruction manualPDF166 KB
KasutusjuhendPDF157 KB
KäyttöohjePDF156 KB
Manuel d'instructionsPDF162 KB
BetriebsanleitungPDF167 KB
Οδηγίες χρήσηςPDF169 KB
HandleidingPDF160 KB
Instruction manual / BetriebsanleitungPDF160 KB
Használati útmutatóPDF161 KB
Manuale di istruzioniPDF160 KB
Lietošanas pamācībaPDF159 KB
Instrukciju vadovasPDF161 KB
Instrukcja obsługiPDF163 KB
Manual de instruçõesPDF161 KB
Manual de utilizarePDF160 KB
Návod na poużitiePDF160 KB
Navodila za uporaboPDF158 KB
Manual de instruccionesPDF161 KB
ManualPDF159 KB
Short instructions, safety information
Firmware release informationPDF55 KB
Technical information
Software Licence InformationPDF241 KB
Application reports
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingPDF470 KB
Application Report - Fieldbus Power Supply Compatible with Process Industry ApplicationsPDF229 KB
Applikationsbericht - Digitale Kommunikation in der Produktion von GrobblechenPDF473 KB
Applikationsbericht - Kompatible Feldbus-Stromversorgung für die ProzessindustriePDF231 KB
Applikationsbericht - Steuerung und Überwachung der Kälteanlagen im Deutschen Elektronen-SynchrotronPDF643 KB
Documents
EULA Pepperl+Fuchs Discovery and Configuration ToolPDF57 KB
End-user software license agreement (EULA) PROFINET GSD Generator for HD2-GTR-4PA.PNPDF41 KB
FieldConnex® PROFINET/PROFIBUS-PA Gateway Driver Library for PCS7, flyerPDF437 KB
Release Notes - DTM Collection FieldConnexPDF203 KB
Release Notes for Pepperl+Fuchs PROFINET GSD-Generator for PROFINET PA Segment Coupler HD2-GTR-4PA.PNPDF194 KB

Approvals+Certificates: HD2-GTR-4PA.PN

CertificatesFile TypeFile Size
Canada FMPDF1000 KB
China SITIIAS CCC Ex CertificatePDF1094 KB
Europe TUV Rheinland ATEX Category 3PDF185 KB
TUV Rheinland IECEx Certificate of Conformity Zone 2LINK---
US FMPDF936 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)PDF1040 KB

Associated Products: HD2-GTR-4PA.PN

Matching System Components
For 2 gateway modules, For PROFIBUS PA, Redundant configuration, Installation in Zone 2/Class I, Div. 2, Spring terminals or screw terminals selectable, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunk, Device coupler location [3]: Zone 1 - high-power trunkpa
4 segments, simplex, individual modules per segment, For PROFIBUS PA, For gateway and power supply modules, High-power trunk: Live work on devices in any hazardous area, Optional advanced diagnostics, IECEx approval, International, Europe, USA, Canada, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa
Accessories
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
User interface for PROFIBUS components, Simple access to measurements, diagnostic and configuration data, Supports any FDT/DTM hostpa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Internet download possiblepa

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

From decisions to planning, installation, and commissioning up to operation and maintenance: Discover how to make the most out of your fieldbus infrastructure …