Serviceline Industrial Sensors
Serviceline Explosion Protection
Not available for purchase
Not available for purchase

Temperature Converter HiD2062

HiD2062
  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Thermocouple or mV inputs
  • Output 4 mA ... 20 mA
  • Sensor breakage detection
  • Simple span and zero selection

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiD2062

General specifications
Signal typeAnalog input
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage20.4 ... 30 V DC bus powered via Termination Board
Rated current30 mA at 24 V, 20 mA output (per channel)
Power dissipation0.6 W at 24 V (per channel)
Input
Connection sidefield side
ConnectionSL2:
5a(+), 7a(-); 1a(+), 1b(-): thermocouples type E, J, K, N, R, S, T
5a(+), 7b(-); 1a(+), 3b(-): thermocouple type B and mV input
5b(+), 7b(-); 3a(+), 3b(-): cold junction compensation (CJC)
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1), type L (GOST)
Cold junction compensationat field terminals
Measurement range-10 ... 100 mV
Span2.6 ... 100 mV
Zero suppression± 500 % of span
Line fault detectionsensor burnout 25 nA, upscale or downscale (selectable)
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Load0 ... 650 Ω
Output signal4 ... 20 mA or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt)
Ripple10 mVrms (at load 250 Ω)
Transfer characteristics
Accuracy< ± 0.1 % of full-scale value (current output)
Influence of temperature< ± 0.01 %/K on zero and span
Influence of load< ± 0.1 % of full-scale value from 0 ... 650 Ω
Rise time/fall timetyp. 150 ms
Linearity< ± 0.1 % of full-scale value (terminal based mV input to mA output of thermocouples)
Compensation error± 0.5 K ± 0.05 K deviation from reference of 20 °C (68 °F)
Galvanic isolation
Output/power supplynone
Indicators/settings
Display elementsLED
Control elementsDIP switch
potentiometer
Factory setting4 ... 20 mA, thermocouple type K, 0 ... 500 °C (273 ... 773 K), upscale burnout
Configurationvia DIP switches
via potentiometer
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Relative humidity5 ... 90 %, non-condensing up to 35 °C (95 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 140 g
Dimensions18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Height106 mm
Width18 mm
Length128 mm
Mountingon termination board
Codingpin 1 and 2 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateCESI 02 ATEX 086
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
InputEx ia, Ex iaD
Voltage13.2 V
Current20 mA
Power66 mW
Supply
Maximum safe voltage250 V AC (Attention! Um is no rated voltage.)
CertificatePF 11 CERT 2109 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc [device in zone 2]
Galvanic isolation
Input/inputsafe electrical isolation acc. to EN 60079-11:2007, voltage peak value 60 V
Input/Outputsafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
CSA approval
Control drawing366-005CS-12B (cCSAus)
IECEx approvalIECEx TUN 04.0012
Approved for[Ex ia] IIC
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210129
ECLASS 12.027210129
ECLASS 11.027210129
ECLASS 10.0.127210129
ECLASS 9.027210129
ECLASS 8.027210190
ECLASS 5.127210107
ETIM 9.0EC002919
ETIM 8.0EC002919
ETIM 7.0EC002919
ETIM 6.0EC002919
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiD2062

Function

This isolated barrier is used for intrinsic safety applications. It is a temperature converter that accepts thermocouple or mV input signals from a hazardous area and converts them to an isolated analog current signal in the safe area.

Input type, range, and error handling parameters are configurable by DIP switches and potentiometers.

Each module is supplied with a cold junction compensator (CJC), which is mounted on the screw terminals of the Termination Board.

The outputs are isolated from the inputs and are referenced to the power supply common.

This module mounts on a HiD Termination Board.

Product Documentation: HiD2062

Language Selection:
Brief InstructionsLanguageFile TypeFile Size
Operating instructions HiD206*ENGPDF612 KB
Safety and Security Documentation
Instruction manualENGPDF168 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiD2062

Language Selection:
CADLanguageFile TypeFile Size
CAD 2-D / CAD 2-DALLZIP16364 KB
CAE
EPLAN macros H-System devices (EMA) / EPLAN-Makros Geräte H-System (EMA)ALLZIP3536 KB

Approvals: HiD2062

Language Selection:
CertificatesCert No.LanguageFile TypeFile Size
Canada, USA CSACoC 70001345ALLPDF136 KB
Europe CESI ATEX Category (1) D ATEX Category (1) GCESI 02 ATEX 086ALLPDF3887 KB
Europe Pepperl+Fuchs ATEX Category 3 GPF 11 CERT 2109 XALLPDF446 KB
TUV Nord IECEx Certificate of ConformityIECEx TUN 04.0012ALLLINK---
Control Drawings
Control drawing CSA / Control drawing CSA   ALLPDF98 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0779BALLPDF50 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.