Serviceline Industrial Sensors
Tél.: +32 (0)3-644 25 00
Support en ligne pour la protection contre le risque d’explosion

PROFIBUS Power Hub, Gateway Module HD2-GTR-4PA

HD2-GTR-4PA
  • PROFIBUS DP V1 / For 4 segments PA
  • Couples PROFIBUS PA devices transparently to PROFIBUS DP
  • Optional redundant configuration
  • Installation in Zone 2/Class I, Div. 2
  • Up to 12 Mbit/s, auto adapting
  • For redundant and non-redundant masters
  • Supports Flying Redundancy (FR)
  • Cyclic/acyclic data exchange

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Téléchargez ici la fiche technique complète en PDF:


Caractéristiques techniques  HD2-GTR-4PA

General specifications
Design / MountingMotherboard based
Supply
Rated voltage19.2 ... 35 V DC
Rated current160 ... 90 mA
Power dissipation3 W
Fieldbus interface
PROFIBUS DP
Connection9-pin Sub-D socket
ProtocolPROFIBUS DP V1
Indicators/operating means
LED Seg 1...4red 2 Hz flashing: PA error, red and LED DP/ERR red: MAU error
LED PWRgreen: Power on
LED DP/ERRred 2 Hz flashing: DP error ; red: Hardware error
LED Red.yellow: redundant operation primary device ; yellow 2 Hz flashing: synchronization or redundancy not available
Galvanic isolation
CH/PROFIBUS DPfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
PROFIBUS DP/Supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
CH/CHfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
All circuits/FEfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Low voltage
Directive 73/23/EECEN 50178 (identical to EN 62103)
Standard conformity
Galvanic isolationIEC 62103
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Housing materialPolycarbonate
Housing width40 mm
Housing height106 mm
Housing depth128 mm
Degree of protectionIP20
Mass250 g
Mountingmotherboard mounting , mounting in any orientation
Data for application in connection with hazardous areas
CertificateTÜV 04 ATEX 2500 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
FM certificateFM 19 US 0015 X and FM 19 CA 0011 X
FM markingAEx/Ex ec IIC T4
IECEx approval
IECEx certificateIECEx TUN 13.0038X
IECEx markingEx nA IIC T4 Gc
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Approvals+Certificates: HD2-GTR-4PA

Statements of complianceIdentificationType de fichierTaille
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2267APDF85 KB
Certificates
Brasil TUV Rheinland BrazilTÜV 13.1135XPDF1359 KB
Canada FMFM 19 CA 0011XPDF356 KB
DNV GL MarineTAA0000272PDF78 KB
EAC Lenpromexpertiza (LPE) EAC TP TC 012/2011EAEC RU C-DE.AA71.B.00037/19PDF2835 KB
Europe TUV Nord ATEX Category 3 GTÜV 04 ATEX 2500XPDF1498 KB
India PESO (India) CCOEA/P/HQ/MH/104/4727 (P383302)PDF706 KB
Russia Belarus Kazakhstan EAC EMC EAC TP TC 012/2011EAEC N RU D-DE.EA11.B.00318PDF2892 KB
USA FMFM 19 US 0015XPDF213 KB
Worldwide TUV Nord Ex nA nC IECEx nAIECEx TUN 13.0038XLINK---

Produits associés : HD2-GTR-4PA

Matching system components
For 2 gateway modules, For PROFIBUS PA, Redundant configuration, Installation in Zone 2/Class I, Div. 2, Spring terminals or screw terminals selectablepa
4 segments, simplex, individual modules per segment, For PROFIBUS PA, For gateway and power supply modules, High-power trunk: Live work on devices in any hazardous area, Optional advanced diagnosticspa
Accessories
User interface for PROFIBUS components, Simple access to measurements, diagnostic and configuration data, Supports any FDT/DTM hostpa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Software for connecting people, information, systems, and devices, For applications developed using .NET, Required to run PACTwarepa

De la prise de décisions à la planification, en passant par l'installation et la mise en service, sans oublier l'exploitation et la maintenance : Découvrez comment tirer le meilleur parti de votre infrastructure de bus de terrain…

Le guide de sélection produit rapide pour les interfaces, la gamme FieldConnex®, et la technologie d'entrées/sorties déportées vous aideront à choisir la bonne technologie et les bons systèmes lors de la conception d'une installation d'usine.