Serviceline Industriële Sensoren
Telefoon +32 3 644 25 00
Serviceline Explosiebeveiliging
Telefoon +32 3 644 25 00

Segment Protector for Cabinet Installation R-SP-E12

R-SP-E12
  • 12 increased safety outputs (Ex e)
  • Short circuit current limitation per output
  • Segment Protector in Zone 1/Div. 2
  • Instruments in Zone 1/Div. 1
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • High power on trunk and spurs

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  R-SP-E12

Productbeschrijving
Segment Protector for Cabinet Installation
General specifications
Design / MountingCabinet installation
Fieldbus connection
Power dissipation250 mW
Main cable (Trunk)
Rated voltage9 ... 32 V DC
Outputs
Number of outputs12
Rated voltagemax. 32 V
Rated currentmax. 40 mA
Short-circuit currentmax. 52 mA
Self current consumptionmax. 9 mA
Voltage drop main cable/outputsmax. 1.3 V
Terminating resistorselectable 100 Ω integrated
Surge protectiontrunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V
Indicators/operating means
LED PWRgreen: Fieldbus voltage > 10 V
LED CHANNEL ERRORred flashing: short-circuit
LED COMyellow: bus activity
LED TERM ONyellow: termination activated
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance5 g , 10 ... 150 Hz
Mechanical specifications
Connection typescrew fixing
Core cross sectionmax. 2.5 mm2 / AWG 12-24
Housing materialPolycarbonate
Degree of protectionIP20
Mass800 g
Dimensions
Height100 mm
Width216 mm
Depth50 mm
MountingDIN rail mounting
Coatingresin filled
Data for application in connection with hazardous areas
EU-type examination certificatePTB 04 ATEX 2100 X
MarkingEx-Hexagon II 2 G Ex e mb IIC T4 Gb
Maximum values
Rated voltage≤ 35 V
Prospective short-circuit current100 A
Directive conformity
Directive 94/9/ECEN 60079-0:2012 , EN 60079-7:2007 , EN 60079-18:2009
International approvals
IECEx approvalIECEx PTB 05.0010X
Approved forEx me II T4
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242601
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: R-SP-E12

Informative Literature: R-SP-E12

Taalkeuze:
LiteratureTaalBestandstypeBestandsgrootte
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: R-SP-E12

Taalkeuze:
Safety and Security DocumentationTaalBestandstypeBestandsgrootte
HandleidingHOLPDF221 KB

Approvals: R-SP-E12

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
Brasil TUV Rheinland Brazil Ex eTÜV 13.1153 XALLPDF1179 KB
China SITIIAS CCC Ex Certificate2021322310003756 (Singapore)ALLPDF831 KB
DNV MarineTAA0000272ALLPDF100 KB
Europe PTB ATEX Category 2 GPTB 04 ATEX 2100XALLPDF374 KB
PTB IECEx Certificate of ConformityIECEx PTB 05.0010XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-0207EHOLHOLPDF1134 KB

Aanverwante producten: R-SP-E12

Matching System Components
Connection of Ex d certified devices, Glass fiber reinforced polyester, impact resistant, IP66, Configurable cable entries for trunk and spurs, International approvals, For FOUNDATION Fieldbus H1 and PROFIBUS PA, Device coupler location: Zone 1 - high-power trunk, Instrument location / spur protection: Zone 1 - increased safety, Function: Device coupler, Design / Mounting: Outside installationpa
Segment Protector Junction Box, Brushed Stainless Steel, Connection of Ex d certified devices, Brushed enclosure, IP66, Configurable cable entries for trunk and spurs, International approvals, For FOUNDATION Fieldbus H1 and PROFIBUS PA, Device coupler location: Zone 1 - high-power trunk, Instrument location / spur protection: Zone 1 - increased safety, Function: Device coupler, Design / Mounting: Outside installationpa

Ethernet-APL zorgt voor een ononderbroken gegevensoverdracht over alle hiërarchische niveaus. Leer meer over deze baanbrekende technologie...

RSS-Meldingen voor PANOS-Updates

Ontvang een automatische melding wanneer een nieuwe software-update voor PANOS, het besturingssysteem voor Ethernet-APL-schakelaars, beschikbaar is: Zodra een update wordt vrijgegeven, ontvangt u via onze RSS-feed onmiddellijk een e-mailbericht in uw inbox.

Van beslissing over planning, installatie en indienstname tot gebruik en onderhoud: Ontdek hoe u het beste uit uw veldbusinfrastructuur kunt halen…