Atendimento ao Cliente da Divisão de Sensores Industriais
Rede de Atendimento - Divisão de Proteção Contra Explosão
Indisponível para Compra
Indisponível para Compra

Temperature Converter HiD2062

HiD2062
  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Thermocouple or mV inputs
  • Output 4 mA ... 20 mA
  • Sensor breakage detection
  • Simple span and zero selection

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Faça o download das folhas de dados em PDF:


Folhas de dados: Dados técnicos do  HiD2062

General specifications
Signal typeAnalog input
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage20.4 ... 30 V DC bus powered via Termination Board
Rated current30 mA at 24 V, 20 mA output (per channel)
Power dissipation0.6 W at 24 V (per channel)
Input
Connection sidefield side
ConnectionSL2:
5a(+), 7a(-); 1a(+), 1b(-): thermocouples type E, J, K, N, R, S, T
5a(+), 7b(-); 1a(+), 3b(-): thermocouple type B and mV input
5b(+), 7b(-); 3a(+), 3b(-): cold junction compensation (CJC)
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1), type L (GOST)
Cold junction compensationat field terminals
Measurement range-10 ... 100 mV
Span2.6 ... 100 mV
Zero suppression± 500 % of span
Line fault detectionsensor burnout 25 nA, upscale or downscale (selectable)
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Load0 ... 650 Ω
Output signal4 ... 20 mA or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt)
Ripple10 mVrms (at load 250 Ω)
Transfer characteristics
Accuracy< ± 0.1 % of full-scale value (current output)
Influence of temperature< ± 0.01 %/K on zero and span
Influence of load< ± 0.1 % of full-scale value from 0 ... 650 Ω
Rise time/fall timetyp. 150 ms
Linearity< ± 0.1 % of full-scale value (terminal based mV input to mA output of thermocouples)
Compensation error± 0.5 K ± 0.05 K deviation from reference of 20 °C (68 °F)
Galvanic isolation
Output/power supplynone
Indicators/settings
Display elementsLED
Control elementsDIP switch
potentiometer
Factory setting4 ... 20 mA, thermocouple type K, 0 ... 500 °C (273 ... 773 K), upscale burnout
Configurationvia DIP switches
via potentiometer
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Relative humidity5 ... 90 %, non-condensing up to 35 °C (95 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 140 g
Dimensions18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Height106 mm
Width18 mm
Length128 mm
Mountingon termination board
Codingpin 1 and 2 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateCESI 02 ATEX 086
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
InputEx ia, Ex iaD
Voltage13.2 V
Current20 mA
Power66 mW
Supply
Maximum safe voltage250 V AC (Attention! Um is no rated voltage.)
CertificatePF 11 CERT 2109 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc [device in zone 2]
Galvanic isolation
Input/inputsafe electrical isolation acc. to EN 60079-11:2007, voltage peak value 60 V
Input/Outputsafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
CSA approval
Control drawing366-005CS-12B (cCSAus)
IECEx approvalIECEx TUN 04.0012
Approved for[Ex ia] IIC
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210129
ECLASS 12.027210129
ECLASS 11.027210129
ECLASS 10.0.127210129
ECLASS 9.027210129
ECLASS 8.027210190
ECLASS 5.127210107
ETIM 9.0EC002919
ETIM 8.0EC002919
ETIM 7.0EC002919
ETIM 6.0EC002919
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiD2062

Product Documentation: HiD2062

Selecione o Idioma:
Brief InstructionsIdiomaTipo de ArquivoTamanho do Arquivo
Operating instructions HiD206*ENGPDF612 KB
Safety and Security Documentation
Manual de instruçõesPORPDF164 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiD2062

Selecione o Idioma:
CADIdiomaTipo de ArquivoTamanho do Arquivo
CAD 2-D / CAD 2-DALLZIP16364 KB
CAE
EPLAN macros H-System devices (EMA) / EPLAN-Makros Geräte H-System (EMA)ALLZIP3536 KB

Approvals: HiD2062

Selecione o Idioma:
CertificatesNúmero do CertificadoIdiomaTipo de ArquivoTamanho do Arquivo
Canada, USA CSACoC 70001345ALLPDF136 KB
Europe CESI ATEX Category (1) D ATEX Category (1) GCESI 02 ATEX 086ALLPDF3887 KB
Europe Pepperl+Fuchs ATEX Category 3 GPF 11 CERT 2109 XALLPDF446 KB
TUV Nord IECEx Certificate of ConformityIECEx TUN 04.0012ALLLINK---
Control Drawings
Control drawing CSA / Control drawing CSA   ALLPDF98 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0779BALLPDF50 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.