Atendimento ao Cliente da Divisão de Sensores Industriais
Rede de Atendimento - Divisão de Proteção Contra Explosão
Indisponível para Compra
Indisponível para Compra

Voltage Repeater HiC2068

HiC2068
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Voltage input 0 mV ... ± 500 mV
  • Voltage output 0 mV ... ± 500 mV
  • Selectable up/downscale sensor breakage detection
  • Fault output signal

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Faça o download das folhas de dados em PDF:


Folhas de dados: Dados técnicos do  HiC2068

General specifications
Signal typeAnalog input
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage20 ... 30 V DC bus powered via Termination Board
Ripplewithin the supply tolerance
Rated current≤ 22 mA
Power dissipation/power consumption0.7 W max.
Lockout voltage> 11 V DC
Input
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-)
Input resistance≥ 1.4 MΩ
Transmission range0 ... ± 500 mV
Offset voltage/current≤ 5 µV / ≤ 5 nA
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-)
Voltage0 ... ± 500 mV
LoadAccuracy figures for infinite load impedance. Additional 0.03 % of span for a load resistance of 10 kΩ
Output resistancemax. 3 Ω
Line fault detectioninput: ± 700 mV
output: ± 1 V
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Fault voltage< Vcc/2 (when connected to Vcc via 10 kΩ pull up resistor)
Transfer characteristics
Deviation
After calibrationat 20 °C (68 °F):
± 30 µV up to ± 100mV/± 0.03 % of the span up to +500 mV/± 0.03 % of the span up to -500 mV
Influence of ambient temperature± 10 µV/K (typical ± 2.5 µV/K)
Absolute< 0.25 K at 30 V voltage supply
BandwidthDC to > 350 Hz (-3 dB)
Settling time< 1 ms
Rise time/fall time< 100 µs
Galvanic isolation
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Height106 mm
Width12.5 mm
Depth128 mm
Mountingon termination board
Codingpin 2, 3 and 4 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 10 ATEX 0031X
MarkingEx-Hexagon II (1)GD, I (M1), [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2]
Voltage5.5 V DC
Current2.4 mA
Power3.3 mW
Supply
Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
CertificateBASEEFA 10 ATEX 0032X
MarkingEx-Hexagon II 3G Ex nA II T4
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approval
Control drawing116-0317 (cULus)
IECEx approval
IECEx certificateIECEx BAS 10.0012X
IECEx BAS 10.0013X
IECEx marking[Zone 0] [Ex ia] IIC, [Ex iaD], [Ex ia] I
Ex nA II T4
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210125
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiC2068

Product Documentation: HiC2068

Selecione o Idioma:
Safety and Security DocumentationIdiomaTipo de ArquivoTamanho do Arquivo
Manual de instruçõesPORPDF164 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiC2068

Selecione o Idioma:
CADIdiomaTipo de ArquivoTamanho do Arquivo
CAD 3-D / CAD 3-DALLSTP2770 KB
CAD Portal / CAD PortalALLLINK---

Approvals: HiC2068

Selecione o Idioma:
CertificatesNúmero do CertificadoIdiomaTipo de ArquivoTamanho do Arquivo
Baseefa IECEx Certificate of ConformityIECEx BAS 10.0012XALLLINK---
Baseefa Type n IECEx Certificate of ConformityIECEx BAS 10.0013XALLLINK---
Canada UL cULE106378 cUL (QUZW7)ALLLINK---
Canada UL cULE106378 cUL (QVAJ7)ALLLINK---
Europe Baseefa ATEX Category (1) GDBaseefa 10 ATEX 0031XALLPDF495 KB
Europe Baseefa II 3 G ATEX Category 3 GBaseefa 10 ATEX 0032XALLPDF452 KB
USA ULE106378 UL (QVAJ)ALLLINK---
USA ULE106378 UL (QUZW)ALLLINK---
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF69 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0778DALLPDF83 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.