Servisní linka pro průmyslové snímače
Servisní linka ochrany před výbuchem

Current/Voltage Converter KFD0-CC-1

KFD0-CC-1
  • 1-channel signal conditioner
  • 24 V DC supply (loop powered)
  • Current or voltage input
  • Output: 4 ... 20 mA
  • Potentiometer or DIP switch selectable ranges
  • Line fault detection (LFD)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Stáhněte si kompletní katalogový list ve formátu PDF:


Výňatek z katalogového listu: Technická data   KFD0-CC-1

General specifications
Signal typeAnalog input
Supply
Rated voltage12 ... 35 V DC loop powered
Power dissipation0.4 W
Input
Connection sidefield side
Connectionterminals 1+, 2-
Current range0 ... 20 mA , load ≤ 50 Ω
Voltage range0 ... 10 V , load ≥ 100 kΩ
Output
Connection sidecontrol side
Connectionterminals 9+, 8-
Load(U -12 V) / 0.02 A
Current output4 ... 20 mA , limited to ≤ 35 mA
Fault signaldownscaling ≤ 3 mA
Transfer characteristics
Deviation
After calibration0.1 % of full-scale value
Temperature effect span: 0.050 % of span /K ; zero point: 0.060 % of span /K
Linearization≤ 0.04 % of full-scale value
Influence of supply voltage6.5 ppm/V
Rise time250 ms
Galvanic isolation
Input/Outputsafe isolation according to EN 50178, rated insulation voltage 253 Veff
Indicators/settings
Control elementsDIP switch
potentiometer
Configurationvia DIP switches
via potentiometer
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Insulation coordinationEN 50178
Galvanic isolationEN 50178
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1
Height107 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210107
ECLASS 12.027210107
ECLASS 11.027210107
ECLASS 10.0.127210107
ECLASS 9.027210107
ECLASS 8.027210107
ECLASS 5.127210107
ETIM 9.0EC002475
ETIM 8.0EC002475
ETIM 7.0EC002475
ETIM 6.0EC002475
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD0-CC-1

Informative Literature: KFD0-CC-1

Výběr jazyka:
LiteratureJazykTyp souboruVelikost souboru
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB

Product Documentation: KFD0-CC-1

Výběr jazyka:
Safety and Security DocumentationJazykTyp souboruVelikost souboru
Návod k poużitíCZEPDF47 KB
Manuals
System ManualENGPDF3694 KB

Design / Simulation: KFD0-CC-1

Výběr jazyka:
CADJazykTyp souboruVelikost souboru
CAD 3-D / CAD 3-DALLSTP105 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ939 KB

Související produkty: KFD0-CC-1

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of field and control signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.