VBA-4E4A-CB1-ZEJ/E2J
  • Integrated communication monitoring function
  • Inputs and outputs short-circuit and overload proof
  • Supply of the inputs and the outputs from AS-Interface
  • Function display for bus, inputs and outputs
  • Connection via removable screw terminals

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Stáhněte si kompletní katalogový list ve formátu PDF:


Výňatek z katalogového listu: Technická data   VBA-4E4A-CB1-ZEJ/E2J

Popis produktu
Printed circuit board module
4 inputs/4 outputs
General specifications
Node typeA/B node
AS-Interface specificationV3.0
Required gateway specificationV3.0
UL File NumberE223772
Indicators/operating means
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of outputs
LED PWRAS-Interface voltage; LED green
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 4 LED yellow
Electrical specifications
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 30 mA (without sensors) / max. 180 mA
Protection classIII
Surge protectionUe: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V
Input current5 mA (typically)
Switching pointaccording to EN 61131-2 Typ 1
0 (unattenuated)≤ 0.5 mA
1 (attenuated)≥ 2 mA
Signal delay< 2 ms (input/AS-Interface)
Output
Number/Type4 electronic outputs, PNP
Supplyfrom AS-Interface
Voltage21 ... 31 V
Current≤ 100 mA per output, ≤ 140 mA total
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
EN 61000-6-4:2007
EN 62026-2:2015
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 50295:1999, IEC 62026-2:2015
InputEN 61131-2:2015
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61326-1:2013
Programming instructions
ProfileS-7.A.7
IO code7
ID codeA
ID1 code7
ID2 code7
Data bits (function via AS-Interface)InputOutput
D0 IN1 OUT1
D1 IN2 OUT2
D2 IN3 OUT3
D3 IN4 OUT4
Parameter bits (programmable via AS-i)function
P0Communication monitoring
P0 = 0 monitoring = off, the outputs maintain the status if communication fails
P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
P1Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
P2Synchronous mode
P2 = 0 synchronous mode on
P2 = 1 synchronous mode off (default settings)
P3not used
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree2
Mechanical specifications
Connectionscrew terminals, removable
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 1.5 mm2
In case of wire end ferrule with plastic sleeve: 0.25 mm2 ... 0.5 mm2
On connection of multiple conductors when using two conductors with the same cross section:
Flexible with twin wire end ferrule:
Mass90 g
Dimensions
Height29 mm
Width51 mm
Length76 mm
Tightening torque of clamping screws0.22 ... 0.25 Nm

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VBA-4E4A-CB1-ZEJ/E2J

Product Documentation: VBA-4E4A-CB1-ZEJ/E2J

Výběr jazyka:
Brief InstructionsJazykTyp souboruVelikost souboru
Instruction leaflet / BeipackzettelALLPDF461 KB

Design / Simulation: VBA-4E4A-CB1-ZEJ/E2J

Výběr jazyka:
CAEJazykTyp souboruVelikost souboru
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ286 KB

Approvals: VBA-4E4A-CB1-ZEJ/E2J

Výběr jazyka:
CertificatesČíslo certifikátuJazykTyp souboruVelikost souboru
US CA ULE87056ALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2715BALLPDF116 KB
Bezplatně ke stažení: Oficiální zpráva o komunikačních protokolech založených na protokolu TCP (PDF)

Tato zdarma poskytovaná oficiální zpráva ve formátu PDF porovnává různé komunikační protokoly založené na protokolu TCP (AMQP, OPC UA, MQTT, REST API), které si našly cestu vzhůru a jsou považovány za faktory umožňující používat IIoT a realizovat průmysl 4.0. Získejte zdarma soubor ke stažení hned teď!

Spínací modul rozvaděče KE5 s rozhraním AS-Interface – Jednoduchá manipulace a vylepšená správa

Unikátní design pouzdra nového spínacího modulu rozvaděče KE5 umožňuje jeho jasnou viditelnost a zjednodušuje montáž, zapojení a údržbu uvnitř rozvaděčů a rozbočovačů.

AS-Interface – sortiment

Seznamte se s kompletním sortimentem našich produktů AS-Interface.