Ex pz purge system 5000Q-02-*

5000Q-02-*
  • Ex pz purge system for Zone 2 and 22, ATEX & IECEx
  • Strong and durable polyester housing withstands most extreme environmental conditions
  • 3 RTD inputs for external temperature monitoring and control
  • LCD for viewing programming and operation modes
  • Fully automatic, Rapid Exchange® purging systems
  • Menu driven programming and field configuration for most applications

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Lataa koko tietolomake PDF-tiedostona:


Ote tietolomakkeesta: Tekniset tiedot  5000Q-02-*

Tuotekuvaus
Ex pz purge system for Zone 2 and 22
General specifications
Operating modefully automatic (FA)
Series5000Q
Number of volume exchangesmin. 5
Hazardous environmentgas or dust
Supply
Rated voltage230 VAC - 230 VAC, 48 ... 62 Hz ± 10%
115 VAC - 115 VAC, 48 ... 62 Hz ± 10%
24 VDC - 24 VDC ± 10%
Power consumption230 VAC - 2.3 VA (without digital valve)
115 VAC - 2.3 VA (without digital valve)
24 VDC - 2.5 W (without digital valve)
Input
Number of sensor connectionsup to 3 sensors per unit
Input I ... III
Input typetemperature input
Sensor typePt100, 2-wire connection
Output
Output I
ConnectionK1, terminals 13, 14, 15
Output typepower supply, (1) SPDT, potential free
Inrush current5 A
Contact loading5 A
Output II
ConnectionK2, terminals 10, 11, 12
Output typealarm, (1) SPDT, potential free
Inrush current5 A
Contact loading3 A
Output III
ConnectionSV1, terminals 16, 17, 18
Output typedigital valve, (1) SPDT, powered contacts from power line
Pneumatic parameters
Protective gas supplyinstrument grade air or inert gas
Pressure requirementmin. 2 bar (29 psi)
Safe pressure- gas 0.25 mbar (0.1" H2O) (Zone 2)
- dust 0.5 mbar (0.2" H2O) (Zone 22)
Purge flow rate- 3.0 mm orifice at 2 bar (29 psig): 105 l/min
- 4.5 mm orifice at 2 bar (29 psig): 220 l/min
Flow rate for leakage compensation0.3 l/min typ. (depends on enclosure seal)
Conformity
Degree of protectionEN 60529
Shock resistanceEN 60068-2
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F) at T4
-20 ... 40 °C (-4 ... 104 °F) at T6
Relative humidity5 ... 95 %, noncondensing
Vibration resistance5 ... 100 Hz , 1 g, 12 m/s2, all axes
Impact resistance30 g, 11 ms, all axes
Mechanical specifications
Cable gland1.5 mm diameter max.
wire size
- power supply and contacts 0.13 ... 2.08 mm
- Pt100 0.08 ... 1.31 mm
Degree of protectionIP65
Material
Housingpolyester
Observation windowsafety glass
CableTerminals 10 to 18, and bypass
Cross section: 16 to 20 AWG (0.5 to 1.5 mm2)
Strip length: 0.31 to 0.35 inches (8 to 9 mm)

Terminals 19 to 24
Cross section: 16 to 20 AWG (0.5 to 1.5 mm2)
Strip length: 0.35 inches (9 mm)

Terminals 2 wire PT100s
Cross section: 18 to 24 AWG (0.25 to 1.0 mm2)
Strip length: 0.33 to 0.37 inches (8.5 to 9.5 mm)
Massapprox. 1.4 kg (3.1 lb)
Dimensions140 x 120 x 90 mm (5.5 x 4.7 x 3.5 inch)
Height120 mm
Width140 mm
Depth90 mm
Data for application in connection with hazardous areas
EU-type examination certificateEPS 10 ATEX 1 263 , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II 3 G Ex nA nC [pz] II T4 -20 °C to +60 °C
Ex-Hexagon II 3 G Ex nA nC [pz] II T6 -20 °C to +40 °C
Ex-Hexagon II 3 D Ex tD A22 [pD] IP64 T70°C
Directive conformity
Directive 94/9/ECEN 60079-0:2006 , EN 60079-2:2007 , EN 60079-15:2005 , EN 61241-0:2004 , EN 61241-1:2004 , EN 61241-4:2006
International approvals
IECEx approvalEx nA nC [pz] IIC T4 Gc
Ex nA nC [pz] IIC T6 Gc
Ex tc [p] IIIC T70 °C Dc IP64
File no: IECEx EPS 11.0010
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027180508
ECLASS 12.027180508
ECLASS 11.027180508
ECLASS 10.0.127180508
ECLASS 9.027180508
ECLASS 8.027180508
ECLASS 5.140050501
ETIM 9.0EC000243
ETIM 8.0EC000243
ETIM 7.0EC000243
ETIM 6.0EC000243
ETIM 5.0EC000243
UNSPSC 12.139121301

Details: 5000Q-02-*

Function

The 5000Q series Ex pz purge and pressurization system allows generalpurpose equipment to be mounted in enclosures and operate safely in Zone 2 or Zone 22 hazardous areas.

The 5000Q operates by controlling and monitoring compressed instrument air or inert gas through the protected enclosure to remove and prevent the accumulation of flammable gas, vapors, or dust.

The 5000Q control unit works with the EPV5000Q vent and is ATEX and IECEx certified for Zone 2 or Zone 22 applications.

Product Documentation: 5000Q-02-*

Language Selection:
ManualsKieliTiedostotyyppiTiedoston koko
5000Q Programming Quick Start GuideENGPDF110 KB
5000Q Series Control System for the Zone 2 Pressurizing SystemENGPDF4331 KB

Design / Simulation: 5000Q-02-*

Language Selection:
CADKieliTiedostotyyppiTiedoston koko
STP file for 5000Q control unit / STP-Datei für 5000Q control unitALLZIP358 KB

Approvals: 5000Q-02-*

Language Selection:
CertificatesSertifikaatin nroKieliTiedostotyyppiTiedoston koko
ATEX CertificateEPS 10 ATEX 1 263ALLPDF2745 KB
IECEx Certificate of ConformityIECEx EPS 11.0010ALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-B089AALLPDF216 KB

Get to know the smartest way to ensure hazardous location protection and configure your individual purge and pressurization system!