Type Z & Ex pz purge and pressurization system 5500 Control Unit

5500 Control Unit
  • 100% automatic purge and pressurization system including purging, temperature and leakage control, alarming and system power
  • Third party approvals for Class I, II, Div. 2 and Zone 2/22
  • Universal mounting
  • RTD inputs for temperature alarm and control
  • Five standard purge programs

Lataa koko tietolomake PDF-tiedostona:


Ote tietolomakkeesta: Tekniset tiedot 5500 Control Unit

Tuotekuvaus
Bebco EPS series Type Z & Ex pz purge and pressurization controller
General specifications
Operating modefully automatic (FA)
Series5500
Number of volume exchanges4 ... 19
Hazardous environmentgas or dust
Supply
Rated voltage100 ... 240 V AC, 0.05 A, 50 ... 60 Hz
20 ... 30 V DC, 0.2 A
Power consumption100 ... 240 V AC - 2.3 VA (without digital valve)
20 ... 30 V DC - 2.5 W (without digital valve)
Electrical specifications
Fuse ratingF2:
AC: 2 A
DC: 3.15 A
F1:
AC: 0.08 A
DC: 0.5 A
Input
Input ITemperature, up to 2 RTDs per unit
ConnectionPt100, 2-wire-connection
Input typetemperature input
Input II1 Bypass
Connectionpassive contact (switch)
Input typemechanical contact
Output
Output I
ConnectionK1, terminals: K1/N0, K1/N0
Output typeenclosure power, (1) SPST
Inrush current6 A
Contact loading6 A at 250 V AC , 30 V DC resistive load, 6 A at 30 V DC
Output II
ConnectionK2, terminals: K2 (NO, C, NC)
Output typealarm, (1) DPST
Inrush current3 A
Contact loading3 A at 250 V AC , 30 V DC resistive load, 3 A at 30 V DC
Output III
Connectiondigital valve, terminals SV
Output type(1) SPDT, powered contacts from supply
0.08 A at 250 VAC
0.5 A at 30 VDC
Inrush current3 A
Indicators/settings
LED indicationMembrane Pad
K1: Green - Contact K1 is energized
K2: Amber - Contact K2 is energized
SV1/encl press.: Blue for safe pressure, Amber for valve on
Bypass: Amber when bypass is active
PT100 error: Red when fault in PT100 sensor
Pneumatic parameters
Protective gas supplyinstrument grade air or inert gas
Safe pressure- gas 0.7 mbar (0.3" H2O)
- dust 1.6 mbar (0.65" H2O)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
RoHS
Directive 2011/65/EU (RoHS)EN 50581:2012
Conformity
Degree of protectionEN 60529
Shock resistanceEN 60068-2
Ambient conditions
Ambient temperature-20 ... 40 °C (-4 ... 104 °F) at T6
-20 ... 60 °C (-4 ... 140 °F) at T4
Relative humidity5 ... 90 %, non-condensing
Vibration resistance5 ... 100 Hz , 1 g, 12 m/s2, all axes
Impact resistance30 g, 11 ms, all axes
Mechanical specifications
Connection typeHigh pressure port: 1/8" NPTF
Low pressure port: 1/8" NPTF
Cable glandWire size
M12 diameter 3 - 6.5mm
M20 diameter 10 - 14mm
RTD/Bypass: (3) M12x1.5
K1, K2, SV1: 'P_C' (3) M20x1.5
Degree of protectionType 4X, IP66
MaterialHousing: 316 stainless steel
Cable Gland: 316 stainless steel or Nickel Plated Brass
Pressure Ports: 316 stainless steel
Membrane Pad: Autotex F200XE
O-ring: EPDM
Massapprox. 2.7 kg (6 lb)
Dimensions165 x 124 x 90 mm (6.5 x 4.9 x 3.5 in)
Data for application in connection with hazardous areas
CertificateDEMKO 14 ATEX 1282X
MarkingEx-Hexagon II 3 G Ex ic ec nC [ic pzc] IIC T4 Gc (-20 °C ≤ Ta ≤ 60 °C)
Ex-Hexagon II 3 G Ex ic ec nC [ic pzc] IIC T6 Gc (-20 °C ≤ Ta ≤ 40 °C)
Ex-Hexagon II 3 D Ex ic tc [ic pzc, IIIC] IIIB T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (external version)
Ex-Hexagon II 3 D Ex ic tc [ic pzc, IIIC] IIIB T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (external version)
Ex-Hexagon II 3 D Ex ic tc [ic pzc] IIIC T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (internal version)
Ex-Hexagon II 3 D Ex ic tc [ic pzc] IIIC T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (internal version)
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-2:2014 ,
EN 60079-7:2015 , EN 60079-31:2014
International approvals
UL approval
cULusUL File E184741
Class I, Division 2, Groups A, B, C, D T4 (-20 °C ≤ Ta ≤ 60 °C)
Class II, Division 2, Groups F, G, T4 (-20 °C ≤ Ta ≤ 60 °C)
Class I, Division 2, Groups A, B, C, D T6 (-20 °C ≤ Ta ≤ 40 °C)
Class II, Division 2, Groups F, G T6 (-20 °C ≤ Ta ≤ 40 °C)
IECEx approvalIECEx UL 14.0019X
Ex ic ec nC [ic pzc] IIC T4 Gc (-20 °C ≤ Ta ≤ 60 °C)
Ex ic ec nC [ic pzc] IIC T6 Gc (-20 °C ≤ Ta ≤ 40 °C)
Ex ic tc [ic pzc, IIIC] IIIB T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (external version)
Ex ic tc [ic pzc, IIIC] IIIB T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (external version)
Ex ic tc [ic pzc] IIIC T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (internal version)
Ex ic tc [ic pzc] IIIC T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (internal version)
General information
Supplementary informationType Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Approvals+Certificates: 5500 Control Unit

CertificatesSertifikaatin nroTiedostotyyppiTiedoston koko
Canada ULRFPW7.E184741LINK---
Canada ULRFPW7.E184741LINK---
Europe UL EU-Type Exam. CertificateDEMKO 14 ATEX 1282XPDF654 KB
India PESO (India) CCOEA/P/HQ/MH/104/3886 (P352034)PDF984 KB
UL IECEx Certificate of ConformityIECEx UL 14.0019XLINK---
USA Certificate ULRFPW.E184741LINK---
USA ULRFPW.E184741LINK---
Control drawings
5500 Pz, Type Z Purge System control drawing / Control drawing UL   PDF130 KB

Liitännäistuotteet: 5500 Control Unit

Accessories
Manifold valve used in CSA and UL certificated installationpa
Manifold valve used in FM and CSA certificated installationpa
Manifold valve used in ATEX and IECEx certificated installationpa
Bebco EPS 5500 series ventpa

Bebco EPS® Purge+Pressurization Technology