Yhteydenotto, Koneautomaatio
+358 20 7861 290
Yhteydenotto, Prosessiautomaatio
+358 20 7861 291
Not available for purchase
Not available for purchase

Trip amplifier 1/209

1/209
  • 4-channel
  • Input 0/4 mA ... 20 mA
  • 4 relay contact outputs
  • Programmable
  • Simple operation via front buttons
  • Lead monitoring
  • Galvanic isolation between input, power supply and contact output
  • With computational function
  • LCD display
  • Self-monitoring

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Lataa koko tietolomake PDF-tiedostona:


Ote tietolomakkeesta: Tekniset tiedot  1/209

Tuotekuvaus
Trip amplifier with 1-4 trip values
General specifications
Signal typeAnalog input
Supply
Connectionz2+, z4-, z6 (PE)
Rated voltage18 ... 30 V DC
18 ... 26.4 V AC
Power consumption1.5 W / 2 VA
Input
ConnectionInput I: d32+, z32-
Input II: d30+, z30-
Input III: d28+, z28-
Input IV: d26+, z26-
Input resistance25 Ω (mA)
10 kΩ (V)
Current range0/4 ... 20 mA (0/1 ... 5 V)
Output
ConnectionOutput I: b8, z8, d8; b10, z10, d10
Output II: b12, z12, d12; b14, z14, d14
Output III: b16, z16, d16; b18, z18, d18
Output IV: b20, z20, d20; b22, z22, d22
Relay
Switching voltage50 V
Switching current2 A AC/DC
Switching power60 VA / 30 W
Mechanical life10 Mio. cycles
Electrical life0.5 Mio. cycles
Response time> 20 ms (variable)
Transfer characteristics
Temperature influence< 0.1 %/10 K
Indicators/settings
Display elementsLED 1: trip value 1
LED 2: trip value 2
LED 3: trip value 3
LED 4: trip value 4
LED green: Power on
Configurationvia RS-485 interface at the front side
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECThe device has been used for the same applications for several years. It therefore features an appropriate electromagnetic field immunity. The device must not be used in new plants.
Ambient conditions
Ambient temperature-10 ... 60 °C (14 ... 140 °F)
Storage temperature-25 ... 80 °C (-13 ... 176 °F)
Relative humidity< 75 % (annual mean)
< 95 % (30 d/year), no moisture condensation
Mechanical specifications
Mass300 g
Dimensions22 x 143 x 193 mm (0.9 x 5.6 x 7.6 inch)
Height143 mm
Width22 mm
Length193 mm
Construction typeEurocard 100 x 160 mm (3.9 x 6.3 inch) acc. to DIN 41494, front panel 4TE, mountable in 19 inch rack
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210122
ECLASS 12.027210122
ECLASS 11.027210122
ECLASS 10.0.127210122
ECLASS 9.027210122
ECLASS 8.027210122
ECLASS 5.127210122
ETIM 9.0EC002654
ETIM 8.0EC002654
ETIM 7.0EC002654
ETIM 6.0EC002654
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: 1/209

Function

The programmable self-monitoring device is used to line monitor external set points, gradients, ratios or min/max selections.

Set points are programmable via front push-buttons or PC.

Input, power supply and relay contact output are galvanically isolated.

Product Documentation: 1/209

Language Selection:
ManualsKieliTiedostotyyppiTiedoston koko
Manual 1/209 / Handbuch 1/209ALLPDF2421 KB

Software: 1/209

Language Selection:
Software ToolsJulkaisutiedotTiedostotyyppiTiedoston koko
Parameterization Software / Parametriersoftware07/2009ZIP41730 KB