Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.
Download the complete datasheet as a PDF:
Product Description | ||
---|---|---|
Fieldbus Diagnostic Handheld |
General specifications | ||
---|---|---|
Design / Mounting | Handheld/mobile | |
Supply | ||
Connection | Fieldbus , Battery , 9V 6LR61 block, type alkaline, carbon-zinc, lithium iron disulfide, nickel-cadmium, nickel-metal hydride, or rechargeable lithium , USB | |
Fieldbus interface | ||
Fieldbus type | FOUNDATION Fieldbus/PROFIBUS PA | |
Rated voltage | 8.5 ... 35 V | |
Rated current | ... 10 mA , if bus powered | |
Indicators/operating means | ||
Display | LC display | |
Keypad | Membrane 8 keys | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Software | ||
Languages | English (default), German (optional), Portuguese (optional), | |
Ambient conditions | ||
Ambient temperature | -20 ... 50 °C (-4 ... 122 °F) | |
Storage temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Connection type | Fieldbus: Cable with test clips and cable with test plugs, 2.5 mm Trigger output: Cable with 2 banana plugs USB: Square type B socket |
|
Degree of protection | IP44 | |
Mass | 500 g | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | ZELM 14 ATEX 0531 | |
Marking | ![]() ![]() ![]() ![]() ![]() |
|
Bus | ||
Type | Fieldbus | |
Type of protection | ia, ib | |
Internal capacitance | < 1.8 nF | |
Internal inductance | < 1.5 µH | |
Voltage | 30 V | |
Bus | ||
Type | Fieldbus | |
Type of protection | ic | |
Internal capacitance | < 1.8 F | |
Internal inductance | < 1.5 µH | |
Voltage | 35 V | |
Outputs | ||
Type | Trigger output | |
Maximum safe voltage | 140 V | |
Interface | ||
Type | USB interface | |
Maximum safe voltage | 253 V | |
Voltage | 6 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 | |
International approvals | ||
CSA approval | CSA 16.70029275 | |
Approved for | Class I, Division 2, Groups A, B, C, D T4 Associated equipment for Class I, Division 1 |
|
IECEx approval | IECEx ZLM 14.0012 | |
Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ic IIC T4 Gc , [Ex ia IIIC Da] , [Ex ic IIIC Dc] |
Manuals | Language | File Type | File Size |
---|---|---|---|
Manual | ENG | 15354 KB | |
Instruction manuals | |||
Инструкции | BUL | 200 KB | |
Návod k poużití | CZE | 0 KB | |
Instruktions manual | DAN | 192 KB | |
Instruction manual | ENG | 66 KB | |
Kasutusjuhend | EST | 188 KB | |
Käyttöohje | FIN | 188 KB | |
Manuel d'instructions | FRA | 59 KB | |
Betriebsanleitung | GER | 68 KB | |
Οδηγίες χρήσης | GRE | 203 KB | |
Handleiding | HOL | 132 KB | |
Instruction manual / Betriebsanleitung | HRV | 191 KB | |
Használati útmutató | HUN | 0 KB | |
Manuale di istruzioni | ITA | 68 KB | |
Lietošanas pamācība | LAV | 191 KB | |
Instrukciju vadovas | LIT | 193 KB | |
Instrukcja obsługi | POL | 0 KB | |
Manual de instruções | POR | 193 KB | |
Manual de utilizare | RON | 192 KB | |
Návod na poużitie | SLK | 193 KB | |
Navodila za uporabo | SLV | 0 KB | |
Manual de instrucciones | SPA | 68 KB | |
Manual | SWE | 0 KB | |
Product information | |||
Release Notes FDH-1 Manager | ENG | 462 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of conformity / EU-Konformitätserklärung | DOC-1076B | 94 KB | |
Certificates | |||
Canada, USA CSA | CSA 16.70029275 | 162 KB | |
EAC Lenpromexpertiza (LPE) EAC TP TC 012/2011 | EAEC RU C-DE.AA71.B.00037/19 | 2835 KB | |
Europe ZELM ATEX | ZELM 14 ATEX 0531 | 778 KB | |
India CCOE | A/P/HQ/MH/104(4016(P358048) | 639 KB | |
Worldwide ZELM IECEx Certificate of Conformity | IECEx ZLM 14.0012 | LINK | --- |
Control drawings | |||
CSA Control Drawing / CSA Control Drawing | 281 KB |
Software Tools | Release Info | File Type | File Size |
---|---|---|---|
FDH-1 Manager / FDH-1 Manager | 1.0.0.461 | ZIP | 49485 KB |
The FieldConnex ® Fieldbus Diagnostic Handheld FDH‑1 is a comprehensive measurement and commissioning tool. The handheld can be connected to any point of a segment. Via display and push buttons, FDH‑1 guides the user through many scenarios of testing. FDH‑1 can record and store data for up to 32 segments with maximum device count without requiring a connection to a PC.
FDH‑1 supports inexperienced and expert users alike through different operating modes. Failure margin checks and device coupler tests help set up the optimum condition of the fieldbus infrastructure and find weak spots in the installation. The expert system and wizards enable easy handling and require little or no training. FDH‑1 supports multiple languages that can be downloaded onto the handheld.
FDH‑1 Manager Software Premium can operate the handheld with enhanced visualization. The software loads data from FDH‑1 and saves data back, to allow for comparisons between actual and planned physical layer attributes.