Serviceline Industrial Sensors
Serviceline Explosion Protection

Solenoid Driver KFD2-VM-Ex1.35.L

KFD2-VM-Ex1.35.L
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Output 15.3 V DC at 17 mA
  • 3 logic inputs with AND/OR logic
  • Service port for isolator function test

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KFD2-VM-Ex1.35.L

Product Description
Output 22.3 V
General specifications
Signal typeDigital Output
Supply
ConnectionPower Rail or terminals 11+, 12-
Rated voltage20 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 52 mA
Power dissipationtyp. 1.2 W
Power consumption< 1.5 W
Input
Connectionterminals 7+, 8+, 9+
Signal level1-signal: 15 ... 30 V DC ; input current: approx. 2.3 mA at 24 V DC
0-signal: 0 ... 5 V DC or open input
Response delay5 ... 30 ms (typical 10 ms)
Output
Internal resistormax. 410 Ω
Limitcurrent IE: ≥ 17 mA; typ. 18 mA
voltage UE: ≥ 15.3 V; typ. 16 V
Open loop voltagemin. 22.3 V
Connectionterminals 4+, 6-
Output rated operating current17 mA
Output signalThese values are valid for the rated operating voltages from 20 ... 30 V DC.
Transfer characteristics
Switching frequency15 Hz
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 150 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Data for application in connection with hazardous areas
EC-Type Examination CertificatePTB 00 ATEX 2132
Group, category, type of protectionEx-Hexagon II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2]
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012

Documents: KFD2-VM-Ex1.35.L

ManualsLanguageFile TypeFile Size
Manual Isolated Barriers K-systemENGPDF760 KB
Manuel pour Barrières Isolées de Système KFRAPDF759 KB
Handbuch Trennbarrieren K-SystemGERPDF745 KB
Manual Isolated Barriers K-systemRUSPDF4107 KB
Instruction manuals
ИнструкцииBULPDF62 KB
Návod k poużitíCZEPDF57 KB
Instruktions manualDANPDF55 KB
Instruction manualENGPDF49 KB
KasutusjuhendESTPDF53 KB
KäyttöohjeFINPDF53 KB
Manuel d'instructionsFRAPDF91 KB
BetriebsanleitungGERPDF51 KB
Οδηγίες χρήσηςGREPDF65 KB
HandleidingHOLPDF67 KB
Instruction manual / BetriebsanleitungHRVPDF65 KB
Használati útmutatóHUNPDF66 KB
Manuale di istruzioniITAPDF89 KB
Lietošanas pamācībaLAVPDF65 KB
Instrukciju vadovasLITPDF65 KB
Instrukcja obsługiPOLPDF68 KB
Manual de instruçõesPORPDF68 KB
Manual de utilizareRONPDF67 KB
Návod na poużitieSLKPDF126 KB
Manual de instruccionesSPAPDF91 KB
ManualSWEPDF63 KB
Technical information
Application Guideline Solenoid DriversENGPDF734 KB
Anwendungsbeschreibung VentilsteuerbausteineGERPDF737 KB

Approvals+Certificates: KFD2-VM-Ex1.35.L

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1949PDF82 KB
Certificates
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe PTB ATEX Category (1) GDPTB 00 ATEX 2132PDF554 KB
Pepperl+Fuchs Functional Safety AssessmentFS-0065PF-20A PDF69 KB
Russia Belarus Kazakhstan EAC EAC TP TC 012/2011EAEC RU C-DE.EX01.B.00102/19PDF9815 KB

Associated Products: KFD2-VM-Ex1.35.L

Accessories

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa

Function: KFD2-VM-Ex1.35.L

This isolated barrier is used for intrinsic safety applications. It supplies power to solenoids and other similar loads.

It is controlled by two "OR" and one "AND" configured logic input.

At full load, 15.3 V at 17 mA is available for the hazardous area load. The output signal has a resistive characteristic.

An override/test jack feature is available on the front plate of the device.

By engaging the service plug, the logic inputs are bypassed and the output is energized. The operation of this test feature is indicated by a red LED.