Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.
Download the complete datasheet as a PDF:
Product Description | ||
---|---|---|
current limit 80 mA |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Rated voltage | loop powered | |
Power dissipation | < 1 W (≤ 30 V) | |
Input | ||
Connection side | control side | |
Connection | terminals 7, 8 | |
Rated voltage | 20 ... 35 V DC | |
Current | 140 mA at 20 V input voltage, load = 140 Ω 100 mA at 35 V input voltage, load = 140 Ω |
|
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Internal resistor | ≤ 150 Ω | |
Current | ≥ 80 mA | |
Voltage | ≥ 11 V | |
Open loop voltage | min. 22.7 V | |
Output rated operating current | 80 mA | |
Output signal | These values are valid for the rated operating voltage 20 ... 35 V DC. | |
Energized/De-energized delay | single operation: typ. 1.7 ms/50 µs; periodical: typ. 5 µs/50 µs | |
Indicators/settings | ||
Display elements | LED | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | UL 61010-1:2004 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | BASEEFA 06 ATEX 0252 | |
Marking | ![]() |
|
Voltage | 25.2 V | |
Current | 184 mA | |
Power | 1.159 W | |
Input | ||
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
Certificate | TÜV 99 ATEX 1499 X | |
Marking | ![]() |
|
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0309 | |
UL approval | ||
Control drawing | 116-0316 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx BAS 06.0058 IECEx CML 19.0093X |
|
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
CAD | File Type | File Size | |
---|---|---|---|
CAD Portal / CAD Portal | LINK | --- | |
Dimension drawing 2-D (DXF) / Abmessungszeichnung 2-D (DXF) | ZIP | 450 KB | |
Dimension drawing 3-D in IGS format / Abmessungszeichnung 3-D im IGS-Format | IGS | 118 KB | |
Dimension drawing 3-D in STP format / Abmessungszeichnung 3-D im STP-Format | STP | 105 KB | |
EPLAN | |||
EPLAN macro EDZ / EPLAN Makro EDZ | EDZ | 46 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of conformity / EU-Konformitätserklärung | DOC-0062C | 58 KB | |
Certificates | |||
Australia Test Safe | ANZEx 17.3006X | 6788 KB | |
Baseefa IECEx Certificate of Conformity | IECEx BAS 06.0058 | LINK | --- |
Brasil TUV Rheinland Brazil | TÜV 13.1129 | 1310 KB | |
CML IECEx Certificate of Conformity | IECEx CML 19.0093X | LINK | --- |
Canada FM Certificate of Conformity | FM 18 CA 0106X | 360 KB | |
Canada UL cUL | E106378 cUL (QUZW7) | LINK | --- |
China NEPSI | GYJ 15.1118 | 2749 KB | |
DNV GL Marine | TAA00001WX | 77 KB | |
EAC EAC TP TC 020/2011 | TC RU C-DE.MH04.B.00397 | 680 KB | |
Europe Baseefa ATEX | Baseefa 06 ATEX 0252 | 5220 KB | |
Europe TUV Nord ATEX Category 3 G | TÜV 99 ATEX 1499X | 1999 KB | |
Japan CML | CML 18 JPN 2001 | 2212 KB | |
Japan TIIS | TC 18536 | 168 KB | |
Korea KOSHA | 15-AV4BO-0595 | 650 KB | |
Russia Belarus Kazakhstan EAC EAC TP TC 012/2011 | EAEC RU C-DE.EX01.B.00102/19 | 9815 KB | |
South Africa MASC | MASC MS/17-0868 | 266 KB | |
USA FM | CoC 3028278 | 43 KB | |
USA UL | E106378 UL (QUZW) | LINK | --- |
exida Functional Safety Assessment | P+F 1109-099-C R028 V1R0 | 380 KB | |
Control drawings | |||
Control Drawing FM / Control Drawing FM | 84 KB | ||
Control drawing UL / Control drawing UL | 41 KB |
This isolated barrier is used for intrinsic safety applications. It supplies power to solenoids, LEDs, and audible alarms located in a hazardous area.
It is loop powered, so the available energy at the output is received from the input signal. The output signal has a resistive characteristic. As a result the output voltage and current are dependent on the load and the input voltage.
At full load, 11 V at 80 mA is available for the hazardous area application.