Solenoid Driver KCD2-SLD-Ex1.1045

KCD2-SLD-Ex1.1045
  • 1-channel isolated barrier
  • 24 V DC supply (bus or loop powered)
  • Output 45 mA at 10 V DC
  • Line fault transparency (LFT)
  • Test pulse immunity
  • Housing width 12.5 mm
  • Up to SIL 3 acc. to IEC 61508

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of KCD2-SLD-Ex1.1045

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Connectionterminals 5+, 6- loop powered
Power Rail or terminals 9+, 10- bus powered
Rated voltage19 ... 30 V DC
loop powered
Input current75 mA at 24 V, 220 Ω load
Power dissipation1.4 W at 24 V, 220 Ω load
Input
Connection sidecontrol side
Connectionterminals 5+, 6-
Test pulse lengthmax. 2 ms from DO card
Signal levelloop powered
1-signal: 19 ... 30 V DC
0-signal: 0 ... 5 V DC
bus powered
1-signal: 15 ... 30 V DC (current limited at 5 mA)
0-signal: 0 ... 5 V DC
Rated current0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card)
1-signal: ≥ 36 mA (minimum load current DO card)
Inrush current< 200 mA , 10 ms loop powered
Output
Connection sidefield side
Connectionterminals 1+, 2-
Internal resistor285 Ω
Currenttyp. 45 mA
Voltagetyp. 10 V
Current limit45 mA
Open loop voltagetyp. 24.6 V
Loadnominal 0.05 ... 18 kΩ
Output IIfault signal
Connectionterminals 7, 8 , non-intrinsically safe
Contact loading30 V DC/ 0.5 A resistive load
Mechanical life105 switching cycles
Energized/De-energized delay≤ 20 ms / ≤ 20 ms
Line fault detectionsignal at short-circuit RB < 25 Ω, lead breakage RB > 50 kΩ ; test current < 500 µA
Galvanic isolation
Output/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output II/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012 , EN 61326-3-2:2008
For further information see system description.
Degree of protectionIEC 60529:2013
Protection against electrical shockEN 61010-1:2010
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateEXA 17 ATEX 0002 X
MarkingEx-Hexagon II 3(1)G Ex nC ec [ia Ga] IIC T4 Gc
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Output IEx ia
Voltage26 V
Current93 mA
Power605 mW
Supply
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Input
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Collective error message
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Galvanic isolation
Output I/other circuitssafe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approvalE106378
Control drawing116-0448 (cULus)
IECEx approval
IECEx certificateIECEx EXA 17.0001X
IECEx markingEx nC ec [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)

Documents: KCD2-SLD-Ex1.1045

ManualsLanguageFile TypeFile Size
Functional Safety ManualENGPDF435 KB
Manual Isolated Barriers K-systemENGPDF760 KB
Manuel pour Barrières Isolées de Système KFRAPDF759 KB
Handbuch Funktionale SicherheitGERPDF436 KB
Handbuch Trennbarrieren K-SystemGERPDF745 KB
Manual Isolated Barriers K-systemRUSPDF4107 KB
Instruction manuals
ИнструкцииBULPDF152 KB
Návod k poużitíCZEPDF147 KB
Instruktions manualDANPDF145 KB
Instruction manualENGPDF76 KB
KasutusjuhendESTPDF142 KB
KäyttöohjeFINPDF142 KB
Manuel d'instructionsFRAPDF147 KB
BetriebsanleitungGERPDF77 KB
Οδηγίες χρήσηςGREPDF155 KB
HandleidingHOLPDF146 KB
Instruction manual / BetriebsanleitungHRVPDF145 KB
Használati útmutatóHUNPDF147 KB
Manuale di istruzioniITAPDF146 KB
Lietošanas pamācībaLAVPDF145 KB
Instrukciju vadovasLITPDF146 KB
Instrukcja obsługiPOLPDF148 KB
Manual de instruçõesPORPDF147 KB
Manual de utilizareRONPDF146 KB
Návod na poużitieSLKPDF146 KB
Navodila za uporaboSLVPDF144 KB
Manual de instruccionesSPAPDF147 KB
ManualSWEPDF143 KB
Technical information
Application Guideline Solenoid DriversENGPDF734 KB
Anwendungsbeschreibung VentilsteuerbausteineGERPDF737 KB

Approvals+Certificates: KCD2-SLD-Ex1.1045

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3545BPDF89 KB
Certificates
Canada UL cULE106378 cUL (QUZW7)LINK---
EAC EAC TP TC 012/2011TC RU C-DE.AA71.B.00291PDF2516 KB
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe EXA ATEX Category (1) D ATEX ATEX Category (M1) ATEX Category (1) G ATEX Category 3 GEXA 17 ATEX 0002XPDF2278 KB
India PESO (India) CCOEA/P/HQ/KA/104/5601 (P426811)PDF1012 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20181210 - E106378 RepRef 20181130PDF406 KB
USA ULE106378 UL (QUZW)LINK---
Worldwide EXAIECEx EXA 17.0001XLINK---
Worldwide exida Functional Safety AssessmentP+F 1408-048-C R045PDF683 KB
Control drawings
Control Drawing UL / Control Drawing UL   PDF89 KB

Associated Products: KCD2-SLD-Ex1.1045

Accessories

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
Interface for Power Rail, Used for redundant configuration, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminalspa
Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication, Connection via spring terminalspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa