Serviceline Industrial Sensors
Serviceline Explosion Protection

Solenoid Driver KCD0-SD3-Ex1.1245.SP

KCD0-SD3-Ex1.1245.SP
  • 1-channel isolated barrier
  • 24 V DC supply (loop powered)
  • Current limit 45 mA at 12 V DC
  • Test pulse immunity
  • Housing width 12.5 mm
  • Connection via spring terminals with push-in connection technology
  • Up to SIL 3 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KCD0-SD3-Ex1.1245.SP

Product Description
current limit 45 mA
General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Connectionloop powered
Rated voltage19 ... 30 V DC loop powered
Power dissipation< 1.3 W
Input
Connection sidecontrol side
Connectionterminals 5+, 6-
Test pulse lengthmax. 2 ms from DO card
Signal level1-signal: 19 ... 30 V DC
0-signal: 0 ... 5 V DC
Rated voltage19 ... 30 V DC
Rated current0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card)
1-signal: ≥ 36 mA (minimum load current DO card)
Inrush current≤ 200 mA after 100 µs
Output
Connection sidefield side
Connectionterminals 1+, 2-
Internal resistorapprox. 240 Ω
Currenttyp. 45 mA
Voltage≥ 12 V
Current limit45 mA
Open loop voltagetyp. 24.6 V
Switching frequencymax. 10 Hz
Energized/De-energized delay28 ms / 10 ms
Galvanic isolation
Output/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012 , EN 61326-3-2:2008
For further information see system description.
Degree of protectionIEC 60529:2013
Protection against electrical shockEN 61010-1:2010
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connectionspring terminals
Massapprox. 150 g
Dimensions12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateEXA 17 ATEX 0002 X
MarkingEx-Hexagon II 3(1)G Ex ec [ia Ga] IIC T4 Gc
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia
Voltage26 V
Current110 mA
Power715 mW
Input
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approvalE106378
Control drawing116-0448 (cULus)
IECEx approval
IECEx certificateIECEx EXA 17.0001X
IECEx markingEx ec [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: KCD0-SD3-Ex1.1245.SP

ManualsLanguageFile TypeFile Size
Functional Safety ManualENGPDF420 KB
Manual Isolated Barriers K-systemENGPDF760 KB
Manuel pour Barrières Isolées de Système KFRAPDF759 KB
Handbuch Funktionale SicherheitGERPDF424 KB
Handbuch Trennbarrieren K-SystemGERPDF745 KB
Manual Isolated Barriers K-systemRUSPDF4107 KB
Instruction manuals
ИнструкцииBULPDF152 KB
Návod k poużitíCZEPDF147 KB
Instruktions manualDANPDF145 KB
Instruction manualENGPDF76 KB
KasutusjuhendESTPDF142 KB
KäyttöohjeFINPDF142 KB
Manuel d'instructionsFRAPDF147 KB
BetriebsanleitungGERPDF77 KB
Οδηγίες χρήσηςGREPDF155 KB
HandleidingHOLPDF146 KB
Instruction manual / BetriebsanleitungHRVPDF145 KB
Használati útmutatóHUNPDF147 KB
Manuale di istruzioniITAPDF146 KB
Lietošanas pamācībaLAVPDF145 KB
Instrukciju vadovasLITPDF146 KB
Instrukcja obsługiPOLPDF148 KB
Manual de instruçõesPORPDF147 KB
Manual de utilizareRONPDF146 KB
Návod na poużitieSLKPDF146 KB
Navodila za uporaboSLVPDF144 KB
Manual de instruccionesSPAPDF147 KB
ManualSWEPDF143 KB
Technical information
Application Guideline Solenoid DriversENGPDF734 KB
Anwendungsbeschreibung VentilsteuerbausteineGERPDF737 KB

Approvals+Certificates: KCD0-SD3-Ex1.1245.SP

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3545BPDF89 KB
Certificates
Canada UL cULE106378 cUL (QUZW7)LINK---
EAC EAC TP TC 012/2011TC RU C-DE.AA71.B.00291PDF2516 KB
EAC EAC TP TC 020/2011TC RU C-DE.MH04.B.00397PDF680 KB
Europe EXA ATEX Category (1) D ATEX ATEX Category (M1) ATEX Category (1) G ATEX Category 3 GEXA 17 ATEX 0002XPDF2278 KB
India PESO (India) CCOEA/P/HQ/KA/104/5601 (P426811)PDF1012 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20181210 - E106378 RepRef 20181130PDF406 KB
USA ULE106378 UL (QUZW)LINK---
Worldwide EXAIECEx EXA 17.0001XLINK---
Worldwide exida Functional Safety Certificateexida Cert P+F 1710137C P0006 C018 V1R0PDF335 KB
Control drawings
Control Drawing UL / Control Drawing UL   PDF89 KB

Function: KCD0-SD3-Ex1.1245.SP

This isolated barrier is used for intrinsic safety applications.

The device supplies power to solenoids, LEDs and audible alarms located in a hazardous area.

The device is loop powered, so the available energy at the output is received from the input signal. The output signal has a resistive characteristic. As a result the output voltage and current are dependent on the load and the input voltage

At full load, 12 V at 45 mA is available for the hazardous area application.