Datasheet excerpt: Technical data of  NCB40-FP-N0-P1

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance40 mm
Installationflush
Assured operating distance0 ... 32 mm
Actual operating distance36 ... 44 mm typ. 40 mm
Reduction factor rAl 0.35
Reduction factor rCu 0.35
Reduction factor r304 0.8
Output type2-wire
Nominal ratings
Installation conditions
F100 mm
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 ... 80 Hz
Hysteresis0 ... 5 typ. 3 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionyes
Current consumption
Measuring plate not detected≥ 3 mA
Measuring plate detected≤ 1 mA
Time delay before availability≤ 20 ms
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd2360 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
Electromagnetic compatibilityNE 21:2007
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval
Equipment protection level GaIECEx PTB 11.0021X
Equipment protection level GbIECEx PTB 11.0021X
Equipment protection level DaIECEx PTB 11.0021X
Equipment protection level MbIECEx PTB 11.0021X
ATEX approval
Equipment protection level GaPTB 00 ATEX 2032 X
Equipment protection level GbPTB 00 ATEX 2032 X
Equipment protection level DaPTB 00 ATEX 2032 X
EAC conformityTR CU 012/2011
FM approval
Control drawing116-0165
UL approval
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0451
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection typescrew terminals
Information for connectionA maximum of two conductors with the same core cross section may be mounted on one terminal connection!
tightening torque 1.2 Nm + 10 %
Core cross-sectionup to 2.5 mm2
Minimum core cross-sectionwithout wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2
Maximum core cross-sectionwithout wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2
Housing materialPBT
Sensing facePBT
Housing basePBT
Degree of protectionIP66 / IP67
General information
Use in the hazardous areasee instruction manuals

Documents: NCB40-FP-N0-P1

Instruction manualsLanguageFile TypeFile Size
ИнструкцииBULPDF178 KB
Návod k poużitíCZEPDF169 KB
Instruktions manualDANPDF169 KB
Instruction manualENGPDF169 KB
KasutusjuhendESTPDF162 KB
KäyttöohjeFINPDF162 KB
Manuel d'instructionsFRAPDF172 KB
BetriebsanleitungGERPDF170 KB
Οδηγίες χρήσηςGREPDF180 KB
HandleidingHOLPDF169 KB
Instruction manual / BetriebsanleitungHRVPDF166 KB
Használati útmutatóHUNPDF173 KB
Manuale di istruzioniITAPDF170 KB
Lietošanas pamācībaLAVPDF167 KB
Instrukciju vadovasLITPDF170 KB
Instrukcja obsługiPOLPDF172 KB
Manual de instruçõesPORPDF171 KB
Manual de utilizareRONPDF172 KB
Návod na poużitieSLKPDF171 KB
Navodila za uporaboSLVPDF166 KB
Manual de instruccionesSPAPDF233 KB
ManualSWEPDF166 KB
Technical information
Technical informationENGPDF166 KB
Technische InformationGERPDF169 KB

Approvals+Certificates: NCB40-FP-N0-P1

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1476PDF266 KB
Certificates
Canada USA CSA Ordinary Location1007121PDF99 KB
Canada USA UL Hazardous LocationE501628:1:1PDF405 KB
Canada USA UL Ordinary Location20170306-E87056PDF407 KB
EU PTB ATEX ia 2G, 1G, 1D s. certificatePTB 00 ATEX 2032 XPDF29293 KB
Russia NANIO "CCVE"TC RU C-DE.AA87.B.00394PDF3971 KB
Worldwide PTB IECEx iaIECEx PTB 11.0021XLINK---
Control drawings
Control Drawing FM / Control Drawing FM   PDF686 KB
Control drawing UL / Control drawing UL   PDF294 KB

Associated Products: NCB40-FP-N0-P1

Accessories

1-channel isolated barrier, 24 V DC supply (Power Rail), Dry contact or NAMUR inputs, Usable as signal splitter (1 input and 2 outputs), Relay contact output, Fault relay contact output, Line fault detection (LFD), Housing width 12.5 mm, Up to SIL 2 acc. to IEC 61508pa

Single-channel terminal amplifier with line breakage detection, input for NAMUR sensors, DC 24 V supply voltage, standardized interface to prevent signal transmission errors, switching state display, LED yellowfa
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.