Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.
Download the complete datasheet as a PDF:
Datasheet excerpt: Technical data of
NCB40-FP-A2-P1-V1
General specifications |
Switching function | complementary |
Output type | PNP |
Rated operating distance | 40 mm |
Installation | flush |
Output polarity | DC |
Assured operating distance | 0 ... 32.4 mm |
Reduction factor rAl | 0.25 |
Reduction factor rCu | 0.23 |
Reduction factor r304 | 0.85 |
Nominal ratings |
Operating voltage | 10 ... 60 V |
Switching frequency | 0 ... 80 Hz |
Hysteresis | typ. 3 % |
Reverse polarity protection | reverse polarity protected |
Short-circuit protection | pulsing |
Voltage drop | ≤ 3 V |
Operating current | 0 ... 200 mA |
Off-state current | 0 ... 0.5 mA |
No-load supply current | ≤ 20 mA |
Operating voltage indicator | LED, green |
Switching state indicator | LED, yellow |
Functional safety related parameters |
MTTFd | 630 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Approvals and certificates |
UL approval | cULus Listed, General Purpose |
CSA approval | cCSAus Listed, General Purpose |
CCC approval | Certified by China Compulsory Certification (CCC) |
Ambient conditions |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Mechanical specifications |
Connection type | Connector M12 x 1 , 4-pin |
Housing material | PBT |
Sensing face | PBT |
Degree of protection | IP68 |
Documents:
NCB40-FP-A2-P1-V1
CAD+CAE:
NCB40-FP-A2-P1-V1
Approvals+Certificates:
NCB40-FP-A2-P1-V1
Associated Products:
NCB40-FP-A2-P1-V1
Accessories |
|
|
|
Female cordset, M12, 4-pin, PUR cablefa |
|
|
|
|
Female cordset, M12, 4-pin, PUR cablefa |
|