Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive sensor NBB5-F33-A2

NBB5-F33-A2
  • 5 mm flush
  • 4-wire DC

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of NBB5-F33-A2

General specifications
Switching functioncomplementary
Output typePNP
Rated operating distance5 mm
Installationflush
Output polarityDC
Assured operating distance0 ... 4.05 mm
Reduction factor rAl 0.3
Reduction factor rCu 0.2
Reduction factor r304 0.6
Nominal ratings
Operating voltage10 ... 30 V DC
Switching frequency0 ... 500 Hz
Hysteresistyp. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionpulsing
Voltage drop≤ 3 V
Operating current0 ... 200 mA
Off-state current0 ... 0.5 mA typ. 0.1 µA
No-load supply current≤ 20 mA
Functional safety related parameters
MTTFd820 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.34 mm2
Housing materialPBT
Sensing facePBT
Housing diameter
Degree of protectionIP67

Documents: NBB5-F33-A2

Technical informationLanguageFile TypeFile Size
Installation conditionsENGPDF117 KB
EinbaubedingungenGERPDF118 KB

Approvals+Certificates: NBB5-F33-A2

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2499BPDF169 KB
Certificates
Canada USA CSA Ordinary Location1007121PDF99 KB
Canada USA UL Ordinary Location20170306-E87056PDF407 KB