Datasheet excerpt: Technical data of  NCN30+U4+N0-V1

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance30 mm
Installationnon-flush
Assured operating distance0 ... 24.3 mm
Actual operating distance27 ... 33 mm typ.
Reduction factor rAl 0.45
Reduction factor rCu 0.42
Reduction factor r304 0.79
Output type2-wire
Nominal ratings
Installation conditions
A10 mm
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 ... 150 Hz
Hysteresis1 ... 15 typ. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionyes
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected≤ 1 mA
Switching state indicatorLED, yellow
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
Electromagnetic compatibilityNE 21:2007
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
FM approval
Control drawing116-0165
UL approval
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0451
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection typeConnector plug M12 x 1 , 4-pin
Housing materialPBT/metal
Sensing facePBT
Degree of protectionIP68
General information
Use in the hazardous areasee instruction manuals

Documents: NCN30+U4+N0-V1

Instruction manualsLanguageFile TypeFile Size
ИнструкцииBULPDF172 KB
Návod k poużitíCZEPDF166 KB
Instruktions manualDANPDF164 KB
Instruction manualENGPDF151 KB
KasutusjuhendESTPDF159 KB
KäyttöohjeFINPDF159 KB
Manuel d'instructionsFRAPDF167 KB
BetriebsanleitungGERPDF151 KB
Οδηγίες χρήσηςGREPDF175 KB
HandleidingHOLPDF165 KB
Instruction manual / BetriebsanleitungHRVPDF163 KB
Használati útmutatóHUNPDF168 KB
Manuale di istruzioniITAPDF166 KB
Lietošanas pamācībaLAVPDF164 KB
Instrukciju vadovasLITPDF165 KB
Instrukcja obsługiPOLPDF167 KB
Manual de instruçõesPORPDF167 KB
Manual de utilizareRONPDF167 KB
Návod na poużitieSLKPDF167 KB
Navodila za uporaboSLVPDF163 KB
Manual de instruccionesSPAPDF229 KB
ManualSWEPDF163 KB
Technical information
Installation conditionsENGPDF210 KB
EinbaubedingungenGERPDF210 KB

Approvals+Certificates: NCN30+U4+N0-V1

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1726APDF101 KB
Certificates
Canada USA CSA Ordinary Location1007121PDF99 KB
Canada USA UL Hazardous LocationE501628:1:1PDF405 KB
Canada USA UL Ordinary Location20170306-E87056PDF407 KB
EU PTB ATEX ia 2G, 1G, 1D s. certificatePTB 00 ATEX 2032 XPDF29293 KB
Worldwide PTB IECEx iaIECEx PTB 11.0021XLINK---
Control drawings
Control Drawing FM / Control Drawing FM   PDF686 KB
Control drawing UL / Control drawing UL   PDF294 KB

Associated Products: NCN30+U4+N0-V1

Accessories

Female cordset, M12, 2-pin, NAMUR, PUR cablefa

Mounting aid for VariKont and +U1+ fa

Female cordset, M12, 2-pin, NAMUR, PUR cablefa
Modular mounting bracket fa
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.