Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive slot sensor SJ10-N

SJ10-N
  • Usable up to SIL 2 acc. to IEC 61508
  • 10 mm slot width


NAMUR sensors must be operated with approved switch amplifiers. Please find suitable devices below:

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  SJ10-N

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Slot width10 mm
Depth of immersion (lateral)13.5 ... 16.5 mm , typ. 15 mm
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Operating voltage5 ... 25 V
Switching frequency0 ... 1000 Hz
Hysteresis0.1 ... 0.5 mm
Current consumption
Measuring plate not detected≥ 3 mA at nominal voltage
Measuring plate detected≤ 1 mA at nominal voltage
Functional safety related parameters
MTTFd11460 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval
Equipment protection level GaIECEx PTB 11.0091X
Equipment protection level GbIECEx PTB 11.0091X
Equipment protection level DaIECEx PTB 11.0091X
Equipment protection level MbIECEx PTB 11.0091X
ATEX approval
Equipment protection level GaPTB 99 ATEX 2219 X
Equipment protection level GbPTB 99 ATEX 2219 X
Equipment protection level DaPTB 99 ATEX 2219 X
FM approval
Control drawing116-0165
UL approvalcULus Listed, General Purpose
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0453
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.75 mm2
Housing materialPBT
Degree of protectionIP67
Cable
Bending radius> 10 x cable diameter
General information
Use in the hazardous areasee instruction manuals

Documents: SJ10-N

Instruction manualsLanguageFile TypeFile Size
ИнструкцииBULPDF177 KB
Návod k poużitíCZEPDF167 KB
Instruktions manualDANPDF166 KB
Instruction manualENGPDF168 KB
KasutusjuhendESTPDF161 KB
KäyttöohjeFINPDF161 KB
Manuel d'instructionsFRAPDF170 KB
BetriebsanleitungGERPDF169 KB
Οδηγίες χρήσηςGREPDF179 KB
HandleidingHOLPDF168 KB
Instruction manual / BetriebsanleitungHRVPDF165 KB
Használati útmutatóHUNPDF172 KB
Manuale di istruzioniITAPDF169 KB
Lietošanas pamācībaLAVPDF166 KB
Instrukciju vadovasLITPDF166 KB
Instrukcja obsługiPOLPDF171 KB
Manual de instruçõesPORPDF169 KB
Manual de utilizareRONPDF169 KB
Návod na poużitieSLKPDF168 KB
Navodila za uporaboSLVPDF165 KB
Manual de instruccionesSPAPDF232 KB
ManualSWEPDF165 KB

Approvals+Certificates: SJ10-N

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1302PDF347 KB
Certificates
Canada USA CSA Ordinary Location1007121PDF99 KB
Canada USA UL Hazardous LocationE501628:1:3PDF405 KB
Canada USA UL Ordinary Location20170306-E87056PDF407 KB
EU PTB ATEX ia 2G, 1G, 1D s. certificatePTB 99 ATEX 2219 XPDF8732 KB
Worldwide PTB IECEx iaIECEx PTB 11.0091XLINK---
Control drawings
Control Drawing FM / Control Drawing FM   PDF686 KB
Control drawing UL / Control drawing UL   PDF168 KB
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.