Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive sensor NBB15-30GM50-US-V12

NBB15-30GM50-US-V12
  • Basic series
  • 15 mm flush
  • 2-wire AC/DC

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  NBB15-30GM50-US-V12

General specifications
Switching functionNormally open (NO)
Output typeTwo-wire
Rated operating distance15 mm
Installationflush
Output polarityAC/DC
Reduction factor rAl 0.5
Reduction factor rCu 0.45
Reduction factor r304 0.75
Output type3-wire
Nominal ratings
Operating voltage20 ... 250 V AC/20 ... 300 V DC
Switching frequency30 Hz
Hysteresis3 ... 15 typ. 5 %
Reverse polarity protectionreverse polarity tolerant
Short-circuit protectionyes
Voltage drop≤ 8 V
Operating current4 ... 500 mA AC/DC
Off-state current≤ 0.8 mA
Operating voltage indicatorLED, green
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd1036 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCertified by China Compulsory Certification (CCC)
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection typeConnector 1/2"-20 UN , 3-pin
Housing materialbrass, nickel-plated
Sensing facePBT
Degree of protectionIP67

Approvals+Certificates: NBB15-30GM50-US-V12

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3067CPDF49 KB
Certificates
Canada USA CSA Ordinary Location1007121PDF99 KB
Canada USA UL Ordinary Location20170306-E87056PDF407 KB

Associated Products: NBB15-30GM50-US-V12

Accessories

Mounting flange, 30 mmfa
Quick mounting bracket with dead stopfa
Connecting cable, 1/2" - 20 UNF, 3-pin, PVC cablefa
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.