Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive sensor NCN8-18GM50-E2-3G-3D-5M

NCN8-18GM50-E2-3G-3D-5M
  • Comfort series
  • ATEX-approval for zone 2 and zone 22

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  NCN8-18GM50-E2-3G-3D-5M

General specifications
Switching functionNormally open (NO)
Output typePNP
Rated operating distance8 mm
Installationnon-flush
Output polarityDC
Assured operating distance0 ... 6.48 mm
Actual operating distance7.2 ... 8.8 mm typ. 8 mm
Reduction factor rAl 0.45
Reduction factor rCu 0.4
Reduction factor r304 0.7
Output type3-wire
Nominal ratings
Operating voltage10 ... 60 V
Switching frequency0 ... 400 Hz
Hysteresis1 ... 10 typ. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionpulsing
Voltage drop≤ 3 V
Voltage drop at IL
Voltage drop IL = 200 mA, switching element on1.5 ... 2.5 V typ. 1.9 V
Operating current0 ... 200 mA
Lowest operating current0 mA
Off-state current0 ... 0.5 mA typ. 0.01 mA
Off-state current TU =40 °C, switching element off≤ 100 µA
No-load supply current≤ 10 mA
Time delay before availability&les
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd1497 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
CCC approvalCertified by China Compulsory Certification (CCC)
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Mechanical specifications
Connection typecable PVC , 5 m
Core cross-section0.5 mm2
Housing materialStainless steel 1.4305 / AISI 303
Sensing facePBT
Degree of protectionIP67
Cable
Bending radius> 10 x cable diameter
Equipment protection level Dc (tc)
Special conditions
Maximum permissible ambient temperature TUmaxdependant of the load current IL and the max. operating voltage UBmax
Information can be taken from the following list.
General information
Use in the hazardous areasee instruction manuals

Documents: NCN8-18GM50-E2-3G-3D-5M

Instruction manualsLanguageFile TypeFile Size
ИнструкцииBULPDF148 KB
Návod k poużitíCZEPDF142 KB
Instruktions manualDANPDF141 KB
Instruction manualENGPDF148 KB
KasutusjuhendESTPDF137 KB
KäyttöohjeFINPDF137 KB
Manuel d'instructionsFRAPDF144 KB
BetriebsanleitungGERPDF149 KB
Οδηγίες χρήσηςGREPDF151 KB
HandleidingHOLPDF140 KB
Instruction manual / BetriebsanleitungHRVPDF140 KB
Használati útmutatóHUNPDF143 KB
Manuale di istruzioniITAPDF141 KB
Lietošanas pamācībaLAVPDF140 KB
Instrukciju vadovasLITPDF142 KB
Instrukcja obsługiPOLPDF144 KB
Manual de instruçõesPORPDF142 KB
Manual de utilizareRONPDF141 KB
Návod na poużitieSLKPDF142 KB
Navodila za uporaboSLVPDF140 KB
Manual de instruccionesSPAPDF142 KB
ManualSWEPDF139 KB
Documents
EPLAN macro EMA / EPLAN Makro EMAALLEMA91 KB

Approvals+Certificates: NCN8-18GM50-E2-3G-3D-5M

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1367APDF52 KB
Certificates
Europe Pepperl+Fuchs ATEX Category 3 D CertificatePF15CERT3774XPDF1001 KB
Europe Pepperl+Fuchs ATEX Category 3 G CertificatePF15CERT3754XPDF1015 KB

Associated Products: NCN8-18GM50-E2-3G-3D-5M

Accessories

Mounting flange, 18 mmfa
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.