Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive sensor NMB3-8GM35-E2

NMB3-8GM35-E2
  • 3 mm flush
  • Stainless steel sensing face
  • Increased operating distance

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  NMB3-8GM35-E2

General specifications
Switching functionNormally open (NO)
Output typePNP
Rated operating distance3 mm
Installationflush
Output polarityDC
Assured operating distance0 ... 2.43 mm
Reduction factor rAl 0.3
Reduction factor rCu 0.2
Reduction factor r304 0.7
Output type3-wire
Nominal ratings
Operating voltage10 ... 30 V DC
Switching frequency0 ... 360 Hz
Hysteresis5 ... 15 typ. 10 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionpulsing
Voltage drop≤ 2 V
Operating current0 ... 100 mA
Off-state current0 ... 10 µA typ. 0.1 µA at 25 °C
No-load supply current≤ 10 mA
Switching state indicatorLED, red
Functional safety related parameters
MTTFd2000 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 75 °C (-13 ... 167 °F)
Mechanical specifications
Connection typecable PUR , 2 m
Core cross-section0.14 mm2
Housing materialStainless steel 1.4305 / AISI 303
Sensing faceStainless steel 1.4305 / AISI 303
Degree of protectionIP67
Cable
Cable diameter3 mm - 0.2 mm
Bending radius> 12 x cable diameter

Documents: NMB3-8GM35-E2

Technical informationLanguageFile TypeFile Size
Installation conditionsENGPDF1053 KB
EinbaubedingungenGERPDF1054 KB
Documents
EPLAN macro EMA / EPLAN Makro EMAALLEMA91 KB

Approvals+Certificates: NMB3-8GM35-E2

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3030APDF71 KB
Certificates
Canada USA CSA Ordinary Location1007121PDF99 KB
Canada USA UL Ordinary Location20170306-E87056PDF407 KB
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.