Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive sensor NCN3-F31-B3B-V1-V1

NCN3-F31-B3B-V1-V1
  • Direct mounting on standard actuators
  • A/B slave with extended addressing possibility for up to 62 slaves
  • Mode of operation, programmable
  • Degree of protection IP67
  • Communication monitoring, turn-off
  • Lead breakage and short-circuit monitoring of the valve

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  NCN3-F31-B3B-V1-V1

Product Description
Valve positioner and valve control module
General specifications
Switching functionNormally open/closed (NO/NC) programmable
Output typeAS-Interface
Rated operating distance3 mm
Installationflush mountable
Assured operating distance0 ... 2.43 mm
Reduction factor rAl 0.5
Reduction factor rCu 0.45
Reduction factor r304 1
Reduction factor rSt37 1.2
Slave typeA/B slave
AS-Interface specificationV3.0
Required master specification≥ V2.1
Nominal ratings
Operating voltage26.5 ... 31.9 V via AS-i bus system
Switching frequency0 ... 100 Hz
No-load supply current≤ 35 mA
Functional safety related parameters
MTTFd842 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Indicators/operating means
LED PWRAS-Interface voltage; LED green
LED INswitching state (input); LED yellow
LED OUTbinary LED yellow/red
yellow: switching state
red: lead breakage/short-circuit
Electrical specifications
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current100 mA
Compliance with standards and directives
Standard conformity
Electromagnetic compatibilityEN 50295:1999-10
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection (system side)4-pin, M12 x 1 connector
Connection (valve side)socket connector , M12 x 1 , 4-pin
Connector housingmetal
Housing materialPBT
Degree of protectionIP67
Notevalve voltage limited to 26,4 V max.; valve power 2,5 W max.

CAD+CAE: NCN3-F31-B3B-V1-V1

CADFile TypeFile Size
3-D model in IGS format / 3-D-Modell im IGS-FormatIGS1637 KB
3-D model in STP format / 3-D-Modell im STP-FormatSTP437 KB
CAD Portal / CAD PortalLINK---

Approvals+Certificates: NCN3-F31-B3B-V1-V1

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2792APDF169 KB
Certificates
Canada USA CSA Ordinary Location1007121PDF99 KB
Canada USA UL Ordinary Location20170306-E87056PDF407 KB

Associated Products: NCN3-F31-B3B-V1-V1

Matching system components

fa

fa
Accessories

Female cordset, M12, 4-pin, PUR cablefa

Female cordset, M12, 4-pin, PUR cablefa

fa
fa
fa
fa
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.