Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive sensor NBB1,5-F41A-E2

NBB1,5-F41A-E2
  • 1.5 mm flush
  • 3-wire DC
  • Metal housing

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of NBB1,5-F41A-E2

General specifications
Switching functionNormally open (NO)
Output typePNP
Rated operating distance1.5 mm
Installationflush
Output polarityDC
Assured operating distance0 ... 1.215 mm
Reduction factor rAl 0.45
Reduction factor rCu 0.35
Reduction factor r304 0.75
Nominal ratings
Operating voltage10 ... 30 V DC
Switching frequency0 ... 1500 Hz
Hysteresistyp. 3 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionpulsing
Voltage drop≤ 3 V
Operating current0 ... 100 mA
Off-state current0 ... 0.5 mA typ.
No-load supply current≤ 15 mA
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd1528 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.14 mm2
Housing materialbrass, nickel-plated
Sensing facePBT
Housing diameter
Degree of protectionIP67
Mass13.5 g

Documents: NBB1,5-F41A-E2

Technical informationLanguageFile TypeFile Size
Installation conditionsENGPDF117 KB
EinbaubedingungenGERPDF118 KB
Documents
EPLAN macro EMA / EPLAN Makro EMAALLEMA91 KB

Approvals+Certificates: NBB1,5-F41A-E2

CertificatesCertificate No.File TypeFile Size
Canada USA CSA Ordinary Location1007121PDF99 KB
Canada USA UL Ordinary Location20170306-E87056PDF407 KB