Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive sensor NBN8-18GM50-E2-T

NBN8-18GM50-E2-T
  • Extended temperature range
  • 8 mm non-flush

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  NBN8-18GM50-E2-T

General specifications
Switching functionNormally open (NO)
Output typePNP
Rated operating distance8 mm
Installationnon-flush
Output polarityDC
Assured operating distance0 ... 6.48 mm
Actuating elementmild steel, e. g. 1.0037, SR235JR (formerly St37-2)
24 mm x 24 mm x 1 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.7
Reduction factor rBrass 0.4
Nominal ratings
Operating voltage10 ... 30 V
Switching frequency0 ... 300 Hz
Hysteresis0.04 ... 1.76 mm
Reverse polarity protectionyes
Short-circuit protectionyes
Overload resistanceyes
Wire breakage protectionyes
Inductive overvoltage protectionyes
Ripple10 %
Voltage drop≤ 2.5 V
Repeat accuracy0.2 mm
Operating current0 ... 200 mA
Off-state current0 ... 0.5 mA typ. 0.1 µA at 25 °C
No-load supply current≤ 7 mA
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd1935 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Approvals and certificates
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection typecable PUR , 2 m
Core cross-section0.25 mm2
Housing materialbrass, nickel-plated
Sensing facePBT
Housing diameter18 mm
Degree of protectionIP67
Mass90 g

Documents: NBN8-18GM50-E2-T

Technical informationLanguageFile TypeFile Size
Installation conditionsENGPDF1054 KB
EinbaubedingungenGERPDF1060 KB
Documents
EPLAN macro EMA / EPLAN Makro EMAALLEMA91 KB

Approvals+Certificates: NBN8-18GM50-E2-T

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-4320PDF184 KB

Associated Products: NBN8-18GM50-E2-T

Accessories

Mounting flange, 18 mmfa
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.