Inductive analog sensor NBN15-30GM60-I3

NBN15-30GM60-I3
  • Inductive analog
  • Output 0 mA ... 20 mA
  • Non-flush

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  NBN15-30GM60-I3

General specifications
Output typeAnalog current output
Installationnon-flush
Output polarityDC
Measurement range5 ... 15 mm
Output type3-wire
Nominal ratings
Operating voltage15 ... 30 V DC
Repeat accuracy0 ... 200 µm
No-load supply current≤ 12 mA
Analog output
Output type0 ... 20 mA
Slope of output characteristic2 mA / mm
Linearity error≤ ± 5 % of full-scale value
Load resistor≤ 500 Ω
Rate of current rise
0 ... 20 mA≤ 17.5 A/s
20 ... 0 mA≤ 16.4 A/s
Temperature drift≤ ± 0.15 %/K of the measured value
Residual ripple± 125 µA
Compliance with standards and directives
Standard conformity
StandardsEN 60947-5-2:2007
IEC 60947-5-2:2007
EN 60947-5-7:2003
IEC 60947-5-7:2003
Approvals and certificates
UL approvalcULus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.75 mm2
Housing materialStainless steel V2A
Sensing facePBT
Degree of protectionIP67
Cable
Cable diameter6.4 mm ± 0.2 mm
Bending radius> 10 x cable diameter

Approvals+Certificates: NBN15-30GM60-I3

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3469PDF185 KB
Certificates
Canada USA UL Ordinary Location20170306-E87056PDF407 KB

Associated Products: NBN15-30GM60-I3

Accessories

Mounting flange, 30 mmfa
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.