Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive analog sensor NBB5-18GM60-I

NBB5-18GM60-I
  • Inductive analog
  • Output 4 mA ... 20 mA
  • Flush mounting

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  NBB5-18GM60-I

General specifications
Output typeAnalog current output
Installationflush
Output polarityDC
Measurement range1 ... 5 mm
Output type3-wire
Nominal ratings
Operating voltage10 ... 30 V DC typ. 20 V DC
Reverse polarity protectionyes
Repeat accuracy0 ... 80 µm
No-load supply current≤ 12 mA
Analog output
Output type4 ... 20 mA
Linearity error≤ ± 5 % of full-scale value
Load resistor≤ 1000 Ω typ. 500 Ω
Temperature drift≤ ± 0.15 %/K of full-scale value
Approvals and certificates
UL approvalcULus Listed, Class 2 Power Source
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.5 mm2
Housing materialbrass, nickel-plated
Sensing facePBT
Degree of protectionIP67

Approvals+Certificates: NBB5-18GM60-I

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3724PDF185 KB
Certificates
Canada USA UL Ordinary Location20170306-E87056PDF407 KB

Associated Products: NBB5-18GM60-I

Accessories

Mounting flange, 18 mmfa
VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.