Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.
Download the complete datasheet as a PDF:
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | Two-wire | |
Rated operating distance | 10 mm | |
Installation | non-flush | |
Output polarity | AC | |
Assured operating distance | 0 ... 7.2 mm | |
Output type | 2-wire | |
Nominal ratings | ||
Installation conditions | ||
A | 0 mm | |
B | 0 mm | |
C | 30 mm | |
F | 50 mm | |
Operating voltage | 20 ... 253 V AC 1) | |
Switching frequency | 0 ... 10 Hz | |
Hysteresis | 2 ... 10 typ. 5 % | |
Reverse polarity protection | reverse polarity tolerant | |
Voltage drop at IL | ||
Voltage drop IL = 100 mA, switching element on | typ. 7 V | |
Momentary current (20 ms, 0.1 Hz) | 0 ... 1200 mA | |
Rated insulation voltage | 1500 V | |
Operating current | 5 ... 200 mA | |
Lowest operating current | 5 mA | |
Off-state current | 0.7 ... 1.5 mA typ. | |
Time delay before availability | ≤ 300 ms | |
Switching state indicator | LED, yellow | |
Indicators/operating means | ||
Potentiometer | sensitivity adjustment | |
Compliance with standards and directives | ||
Standard conformity | ||
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
|
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CCC approval | Certified by China Compulsory Certification (CCC) | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 2 m | |
Core cross-section | 0.75 mm2 | |
Housing material | Stainless steel 1.4305 / AISI 303 | |
Sensing face | PBT | |
Degree of protection | IP67 | |
Note | 1) In the temperature range below 0 °C, permissible operating voltage Ub 80...253 V Safety fuse ≤ 0.8 A (quick-blow) according to IEC 60127-2 Sheet 1 Recommendation: after a short circuit, check that the device is functioning correctly. |
Technical information | Language | File Type | File Size |
---|---|---|---|
Installation conditions | ENG | 219 KB | |
Einbaubedingungen | GER | 345 KB |
CAD | File Type | File Size | |
---|---|---|---|
3-D model in IGS format / 3-D-Modell im IGS-Format | IGS | 72 KB | |
3-D model in STP format / 3-D-Modell im STP-Format | STP | 55 KB | |
CAD Portal / CAD Portal | LINK | --- |
Certificates | Certificate No. | File Type | File Size |
---|---|---|---|
Canada USA UL Ordinary Location | 20170306-E87056 | 407 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|