Capacitive sensor CJ4-12GK-N-Y235563

CJ4-12GK-N-Y235563
  • 4 mm non-flush
  • Custom cable length
  • Customer specific connector


NAMUR sensors must be operated with approved switch amplifiers. Please find suitable devices below:

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  CJ4-12GK-N-Y235563

General specifications
Switching functionNormally open (NO)
Output typeNAMUR
Rated operating distance4 mm
Installationnon-flush
Assured operating distance0 ... 2.88 mm
Output type2-wire
Nominal ratings
Installation conditions
A20 mm
B80 mm
C12 mm
F70 mm
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Operating voltage7 ... 12 V
Switching frequency0 ... 1 Hz
Current consumption
Measuring plate not detected≤ 1 mA
Measuring plate detected≥ 2.4 mA
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007
IEC 60947-5-2:2007
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated ≤36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection typecable PVC , 55 mm with Connector, 99-3431-216-04, Binder
Core cross-section0.34 mm2
Housing materialPBT
Sensing facePBT
Degree of protectionIP68
Cable
Bending radius> 10 x cable diameter
General information
Supplementary informationNote!
When making the electrical connection, ensure that the sensor cable is protected against mechanical stress!
Use in the hazardous areasee instruction manuals

Documents: CJ4-12GK-N-Y235563

Instruction manualsLanguageFile TypeFile Size
ИнструкцииBULPDF167 KB
Návod k poużitíCZEPDF159 KB
Instruktions manualDANPDF157 KB
Instruction manualENGPDF159 KB
KasutusjuhendESTPDF152 KB
KäyttöohjeFINPDF151 KB
Manuel d'instructionsFRAPDF161 KB
BetriebsanleitungGERPDF159 KB
Οδηγίες χρήσηςGREPDF168 KB
HandleidingHOLPDF158 KB
Instruction manual / BetriebsanleitungHRVPDF156 KB
Használati útmutatóHUNPDF160 KB
Manuale di istruzioniITAPDF159 KB
Lietošanas pamācībaLAVPDF156 KB
Instrukciju vadovasLITPDF158 KB
Instrukcja obsługiPOLPDF160 KB
Manual de instruçõesPORPDF160 KB
Manual de utilizareRONPDF161 KB
Návod na poużitieSLKPDF160 KB
Navodila za uporaboSLVPDF156 KB
Manual de instruccionesSPAPDF221 KB
ManualSWEPDF156 KB
Technical information
Installation conditionsENGPDF219 KB
EinbaubedingungenGERPDF345 KB

Approvals+Certificates: CJ4-12GK-N-Y235563

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-4380PDF176 KB
Certificates
Canada USA CSA Ordinary Location1007121PDF99 KB
Canada USA UL Ordinary Location20170306-E87056PDF407 KB
EU TUV Nord ATEX ia 2G, 1G, 1D s. certificateTÜV 03 ATEX 2003 XPDF10461 KB

Associated Products: CJ4-12GK-N-Y235563

Accessories

Mounting flange, 12 mmfa