Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 18 ... 30 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | ≤ 1 W at maximum load | |
Power consumption | ≤ 1.6 W at maximum load | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2-, 3 | |
Input signal | 0/4 ... 20 mA | |
Open circuit voltage/short-circuit current | terminals 1+, 3: 23 V / 25 mA | |
Input resistance | max. 265 Ω terminals 2-, 3 , max. 330 Ω terminals 1+, 3 | |
Available voltage | ≥ 16 V at 20 mA ; ≥ 20 V at 4 mA , terminals 1+, 3 | |
Output | ||
Connection side | control side | |
Connection | terminals 7+, 8-, 9- (sink) terminals 7-, 8+, 9+ (source) see additional information |
|
Load | 0 ... 800 Ω | |
Output signal | 0/4 ... 20 mA (overload > 25 mA) | |
Ripple | max. 50 µA eff | |
External supply (loop) | 2 ... 30 V DC | |
Transfer characteristics | ||
Deviation | at 20 °C (68 °F), 0/4 ... 20 mA ≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
|
Influence of ambient temperature | ≤ 0.25 µA/K | |
Frequency range | input to output: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB) output to input: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB) |
|
Settling time | 200 µs | |
Rise time/fall time | 100 µs | |
Galvanic isolation | ||
Input/Output | basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff | |
Input/power supply | basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff | |
Output/power supply | functional insulation, rated insulation voltage 50 V AC | |
Indicators/settings | ||
Display elements | LED | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 EN 61326-3-2:2008 |
|
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | UL 61010-1:2012 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 200 g | |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |
Accessories | ||
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03) |
Manuals | Language | File Type | File Size |
---|---|---|---|
Functional Safety Manual | ENG | 697 KB | |
Manual Signal Conditioners K-System | ENG | 694 KB | |
Handbuch Funktionale Sicherheit | GER | 664 KB | |
Handbuch Signaltrenner K-System | GER | 698 KB | |
Manual Signal Conditioners K-System | RUS | 3736 KB | |
Instruction manuals | |||
Инструкции | BUL | 53 KB | |
Návod k poużití | CZE | 47 KB | |
Instruktions manual | DAN | 47 KB | |
Instruction manual | ENG | 41 KB | |
Kasutusjuhend | EST | 44 KB | |
Käyttöohje | FIN | 44 KB | |
Manuel d'instructions | FRA | 79 KB | |
Betriebsanleitung | GER | 43 KB | |
Οδηγίες χρήσης | GRE | 55 KB | |
Handleiding | HOL | 56 KB | |
Instruction manual / Betriebsanleitung | HRV | 55 KB | |
Használati útmutató | HUN | 55 KB | |
Manuale di istruzioni | ITA | 77 KB | |
Lietošanas pamācība | LAV | 54 KB | |
Instrukciju vadovas | LIT | 55 KB | |
Instrukcja obsługi | POL | 57 KB | |
Manual de instruções | POR | 56 KB | |
Manual de utilizare | RON | 56 KB | |
Návod na poużitie | SLK | 115 KB | |
Manual de instrucciones | SPA | 79 KB | |
Manual | SWE | 53 KB |
CAD | File Type | File Size | |
---|---|---|---|
CAD Portal / CAD Portal | LINK | --- | |
Dimension drawing 2-D (DXF) / Abmessungszeichnung 2-D (DXF) | ZIP | 507 KB | |
Dimension drawing 3-D in IGS format / Abmessungszeichnung 3-D im IGS-Format | IGS | 209 KB | |
Dimension drawing 3-D in STP format / Abmessungszeichnung 3-D im STP-Format | STP | 179 KB | |
EPLAN | |||
EPLAN Data Portal / EPLAN Data Portal | LINK | --- | |
EPLAN macro P+F.KFD2-STC5-1 / EPLAN-Makro P+F.KFD2-STC5-1 | EDZ | 69 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of conformity / EU-Konformitätserklärung | DOC-3647 | 373 KB | |
Certificates | |||
Belarus Pattern Approval | Nr. 11709 | 15640 KB | |
Canada UL cUL | E106378 cUL (QUZW7) | LINK | --- |
Canada UL cUL | E106378 cUL (QVAJ7) | LINK | --- |
EAC EAC TP TC 020/2011 | TC RU C-DE.MH04.B.00397 | 680 KB | |
Russia VNIIMS | DE.C.34.004.A No.64324/1 | 10397 KB | |
USA UL | E106378 UL (QUZW) | LINK | --- |
USA UL | E106378 UL (QVAJ) | LINK | --- |
Worldwide TUV Rheinland | 968/FSP 1498.00/17 EN | 679 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
This signal conditioner provides the galvanic isolation between field circuits and control circuits.
The device supplies 2-wire and 3-wire SMART transmitters, and can also be used with 2-wire SMART current sources.
It transfers the analog input signal as an isolated current value.
Digital signals may be superimposed on the input signal on the field side or on the control side and are transferred bi-directionally.
The device provides a sink mode or a source mode output on the control side terminals.
The device has an internal resistor. Use this resistor if the HART communication resistance in the control circuit is too low.
Test sockets for the connection of HART communicators are integrated into the terminals of the device.