Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

Universal Temperature Converter KCD2-UT2-1

KCD2-UT2-1
  • 1-channel signal conditioner
  • 24 V DC supply (Power Rail)
  • Thermocouple, RTD, potentiometer or voltage input
  • Current output 0/4 mA ... 20 mA
  • Sink or source mode
  • Configurable by PACTware
  • Line fault (LFD) and sensor burnout detection
  • Up to SIL 2 acc. to IEC 61508/IEC 61511

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of KCD2-UT2-1

Product Description
Current output 0/4 mA ... 20 mA
General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Connectionterminals 9+, 10- or power feed module/Power Rail
Rated voltage19 ... 30 V DC
Ripplewithin the supply tolerance
Power dissipation/power consumption≤ 0.98 W / 0.98 W
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Connectionterminals 1, 2, 3, 4
RTDtype Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
Measuring currentapprox. 200 µA with RTD
Types of measuring2-, 3-, 4-wire connection
Lead resistancemax. 50 Ω per line
Measurement loop monitoringsensor breakage, sensor short-circuit
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)
Cold junction compensationexternal and internal
Measurement loop monitoringsensor breakage
Potentiometer0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
Voltageselectable within the range -100 ... 100 mV
Input resistance≥ 1 MΩ (-100 ... 100 mV)
Output
Connection sidecontrol side
Connectionterminal 5: source (-), terminal 6: source (+), terminal 7: sink(-), terminal 8: sink (+)
OutputAnalog current output
Current range0 ... 20 mA or 4 ... 20 mA
Fault signaldownscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
Sourceload 0 ... 550 Ω
open-circuit voltage ≤ 18 V
SinkVoltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V,
series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage.
The maximum value of the resistance is (V - 5)/0.0215 Ω.
Transfer characteristics
Deviation
After calibrationPt100: ± (0.06 % of measurement value in K + 0.1 % of span + 0.1 K (4-wire connection))
thermocouple: ± (0.05 % of measurement value in °C + 0.1 % of span + 1.5 K (1.7 K for types R and S))
this includes ± 1.3 K error of the cold junction compensation
mV: ± (50 µV + 0.1 % of span)
potentiometer: ± (0.05 % of full scale + 0.1 % of span, (excludes errors due to lead resistance))
Influence of ambient temperaturedeviation of CJC included:
Pt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ΔTamb*)
thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ΔTamb*)
mV: ± (0.01 % of measurement value + 0.006 % of span)/K ΔTamb*)
potentiometer: ± 0.006 % of span/K ΔTamb*)
*) ΔTamb = ambient temperature change referenced to 23 °C (296 K)
Influence of supply voltage< 0.01 % of span
Influence of load≤ 0.001 % of output value per 100 Ω
Reaction timeworst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s
Galvanic isolation
Input/Other circuitsbasic insulation according to IEC 61010-1, rated insulation voltage 300 Veff
Output/supply, programming inputfunctional insulation, rated insulation voltage 50 V AC
There is no electrical isolation between the programming input and the supply.
The programming cable provides galvanic isolation so that ground loops are avoided.
Indicators/settings
Display elementsLEDs
Configurationvia PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: KCD2-UT2-1

ManualsLanguageFile TypeFile Size
Functional Safety ManualENGPDF1542 KB
Installation and configuration guide Device Type Manager (DTM)ENGPDF8665 KB
Manual KCD2-UT2-(Ex)1ENGPDF1060 KB
Manual Signal Conditioners K-SystemENGPDF694 KB
Handbuch Funktionale SicherheitGERPDF1547 KB
Handbuch KCD2-UT2-(Ex)1GERPDF1444 KB
Handbuch Signaltrenner K-SystemGERPDF698 KB
Installations- und Konfigurationsanleitung Device Type Manager (DTM)GERPDF8463 KB
Manual Signal Conditioners K-SystemRUSPDF3736 KB
Instructions, short instructions, safety information
ИнструкцииBULPDF53 KB
Návod k poużitíCZEPDF47 KB
Instruktions manualDANPDF47 KB
Instruction manualENGPDF41 KB
KasutusjuhendESTPDF44 KB
KäyttöohjeFINPDF44 KB
Manuel d'instructionsFRAPDF79 KB
BetriebsanleitungGERPDF43 KB
Οδηγίες χρήσηςGREPDF55 KB
HandleidingHOLPDF56 KB
Instruction manual / BetriebsanleitungHRVPDF55 KB
Használati útmutatóHUNPDF55 KB
Manuale di istruzioniITAPDF77 KB
Lietošanas pamācībaLAVPDF54 KB
Instrukciju vadovasLITPDF55 KB
Instrukcja obsługiPOLPDF57 KB
Manual de instruçõesPORPDF56 KB
Manual de utilizareRONPDF56 KB
Návod na poużitieSLKPDF115 KB
Manual de instruccionesSPAPDF79 KB
ManualSWEPDF53 KB

Approvals+Certificates: KCD2-UT2-1

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-0165APDF311 KB
Certificates
Belarus Pattern ApprovalNr. 11709PDF15640 KB

Software: KCD2-UT2-1

Device type managersRelease InfoFile TypeFile Size
DTM Collection Interface Technology 2 / DTM Collection Interface Technology 21.4.110.71ZIP33316 KB
Software Tools
PACTware 4.1 SP5 / PACTware 4.1 SP54.1.0.52ZIP50675 KB
PACTware 5.0 / PACTware 5.05.0.3.2ZIP56301 KB

Associated Products: KCD2-UT2-1

Accessories
For K-, E- and H-System, Frame application, like e. g. PACTware, must be installed separatelypa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Internet download possiblepa