Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

RTD Converter KFD0-TR-1

KFD0-TR-1
  • 1-channel signal conditioner
  • 24 V DC supply (loop powered)
  • 2- or 3-wire Pt100 RTD input
  • Output 4 mA ... 20 mA, temperature linearization selectable
  • DIP switch selectable ranges
  • Sensor breakage detection

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of KFD0-TR-1

General specifications
Signal typeAnalog input
Supply
Rated voltage12 ... 35 V DC loop powered
Power dissipation0.4 W
Input
Connection sidefield side
Connectionterminals 1, 2-, 3+
suitable for Pt100, 2- and 3-wire connection
Lead resistancemax. 100 Ω per line
Measuring currentapprox. 1 mA
Output
Connection sidecontrol side
Connectionterminals 9+, 8-
Load(U -12 V) / 0.02 A
Current output4 ... 20 mA , limited to ≤ 35 mA
Fault signalsensor burnout: upscaling ≥ 22 mA , limited to ≤ 35 mA
Transfer characteristics
Measurement rangespan without linearization 25 ... 800 °C (77 ... 1472 °F)/ with linearisation 25 ... 375 °C (77 ... 707 °F)
zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/ with linearisation -30 ... 375 °C (-22 ... 707 °F)
span and zero point adjustable
Deviation
After calibration0.1 % of full-scale value
Influence of ambient temperaturespan and zero point 0.015 % / K or ± 10 mΩ / K
Influence of supply voltage6.5 ppm/V
Rise time250 ms
Galvanic isolation
Input/Outputsafe isolation acc. to DIN VDE 0106, rated insulation voltage 253 Veff
Indicators/settings
Control elementsDIP-switch
rotary switch
Configurationvia DIP switches
via rotary switch
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Insulation coordinationEN 50178
Galvanic isolationEN 50178
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: KFD0-TR-1

ManualsLanguageFile TypeFile Size
Manual Signal Conditioners K-SystemENGPDF694 KB
Handbuch Signaltrenner K-SystemGERPDF698 KB
Manual Signal Conditioners K-SystemRUSPDF3736 KB
Instructions, short instructions, safety information
ИнструкцииBULPDF53 KB
Návod k poużitíCZEPDF47 KB
Instruktions manualDANPDF47 KB
Instruction manualENGPDF41 KB
KasutusjuhendESTPDF44 KB
KäyttöohjeFINPDF44 KB
Manuel d'instructionsFRAPDF79 KB
BetriebsanleitungGERPDF43 KB
Οδηγίες χρήσηςGREPDF55 KB
HandleidingHOLPDF56 KB
Instruction manual / BetriebsanleitungHRVPDF55 KB
Használati útmutatóHUNPDF55 KB
Manuale di istruzioniITAPDF77 KB
Lietošanas pamācībaLAVPDF54 KB
Instrukciju vadovasLITPDF55 KB
Instrukcja obsługiPOLPDF57 KB
Manual de instruçõesPORPDF56 KB
Manual de utilizareRONPDF56 KB
Návod na poużitieSLKPDF115 KB
Manual de instruccionesSPAPDF79 KB
ManualSWEPDF53 KB

Approvals+Certificates: KFD0-TR-1

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-2203PDF649 KB
Certificates
Belarus Pattern ApprovalNr. 11709PDF15640 KB
Russia VNIIMS Pattern ApprovalDE.C.32.004.A No.53706PDF2253 KB