General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Rated voltage | 12 ... 35 V DC loop powered | |
Power dissipation | 0.4 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Current range | 0 ... 20 mA , load ≤ 50 Ω | |
Voltage range | 0 ... 10 V , load ≥ 100 kΩ | |
Output | ||
Connection side | control side | |
Connection | terminals 9+, 8- | |
Load | (U -12 V) / 0.02 A | |
Current output | 4 ... 20 mA , limited to ≤ 35 mA | |
Fault signal | downscaling ≤ 3 mA | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of full-scale value | |
Temperature effect | span: 0.050 % of span /K ; zero point: 0.060 % of span /K | |
Linearization | ≤ 0.04 % of full-scale value | |
Influence of supply voltage | 6.5 ppm/V | |
Rise time | 250 ms | |
Galvanic isolation | ||
Input/Output | safe isolation according to EN 50178, rated insulation voltage 253 Veff | |
Indicators/settings | ||
Control elements | DIP-switch potentiometer |
|
Configuration | via DIP switches via potentiometer |
|
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Insulation coordination | EN 50178 | |
Galvanic isolation | EN 50178 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Manuals | Language | File Type | File Size |
---|---|---|---|
Manual Signal Conditioners K-System | ENG | 694 KB | |
Handbuch Signaltrenner K-System | GER | 698 KB | |
Manual Signal Conditioners K-System | RUS | 3736 KB | |
Instruction manuals | |||
Инструкции | BUL | 53 KB | |
Návod k poużití | CZE | 47 KB | |
Instruktions manual | DAN | 47 KB | |
Instruction manual | ENG | 41 KB | |
Kasutusjuhend | EST | 44 KB | |
Käyttöohje | FIN | 44 KB | |
Manuel d'instructions | FRA | 79 KB | |
Betriebsanleitung | GER | 43 KB | |
Οδηγίες χρήσης | GRE | 55 KB | |
Handleiding | HOL | 56 KB | |
Instruction manual / Betriebsanleitung | HRV | 55 KB | |
Használati útmutató | HUN | 55 KB | |
Manuale di istruzioni | ITA | 77 KB | |
Lietošanas pamācība | LAV | 54 KB | |
Instrukciju vadovas | LIT | 55 KB | |
Instrukcja obsługi | POL | 57 KB | |
Manual de instruções | POR | 56 KB | |
Manual de utilizare | RON | 56 KB | |
Návod na poużitie | SLK | 115 KB | |
Manual de instrucciones | SPA | 79 KB | |
Manual | SWE | 53 KB |
CAD | File Type | File Size | |
---|---|---|---|
CAD Portal / CAD Portal | LINK | --- | |
Dimension drawing 2-D (DXF) / Abmessungszeichnung 2-D (DXF) | ZIP | 507 KB | |
Dimension drawing 3-D in IGS format / Abmessungszeichnung 3-D im IGS-Format | IGS | 209 KB | |
Dimension drawing 3-D in STP format / Abmessungszeichnung 3-D im STP-Format | STP | 179 KB | |
EPLAN | |||
EPLAN macro EDZ / EPLAN Makro EDZ | EDZ | 47 KB | |
Prolist | |||
Prolist device specification / Prolist Gerätespezifikation | XML | 23 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of conformity / EU-Konformitätserklärung | DOC-3038 | 296 KB | |
Certificates | |||
Belarus Pattern Approval | Nr. 11709 | 15640 KB | |
Russia VNIIMS Pattern Approval | OC.C.34.004.A No.56757 | 6680 KB |
This signal conditioner converts a 2-wire voltage or current to a 4 mA ... 20 mA signal and provides isolation for non-intrinsically safe applications.
The device can be used to double signals in 20 mA measurement circuits due to the limited current signal input load of 50 Ω.
DIP switches and potentiometers make field calibration easy.
Since this isolator is loop-powered, use the technical data to verify that the proper voltage is available to the field devices.