General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | loop powered | |
Rated voltage | 19 ... 30 V DC loop powered | |
Power dissipation | < 1.5 W | |
Power consumption | < 1.5 W | |
Input | ||
Connection side | control side | |
Connection | Input terminals 5, 6 ; test input terminals 7, 8, 9, 10 | |
Pulse/Pause ratio | 150 ms / 150 ms | |
Test pulse length | max. 4 ms from DO card | |
Test input | see Functional Safety Manual | |
Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V |
|
Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) |
|
Output | ||
Connection side | field side | |
Connection | terminals 1, 2 | |
Contact loading | 253 V AC/3 A/cos φ 0.7; 30 V DC/3 A resistive load 253 V AC / 1/8 HP |
|
Minimum switch current | 10 mA / 24 V DC | |
Energized/De-energized delay | 150 ms / 150 ms | |
Mechanical life | 5 x 106 switching cycles | |
Transfer characteristics | ||
Switching frequency | < 3 Hz | |
Galvanic isolation | ||
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-1:2008 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. |
|
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 15 CERT 3932 X | |
Marking | ![]() |
|
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-15:2010 | |
International approvals | ||
UL approval | E106378 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |
Accessories | ||
Optional accessories | - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03) |
Manuals | Language | File Type | File Size |
---|---|---|---|
Functional Safety Manual | ENG | 401 KB | |
Manual Signal Conditioners K-System | ENG | 694 KB | |
Handbuch Funktionale Sicherheit | GER | 397 KB | |
Handbuch Signaltrenner K-System | GER | 698 KB | |
Manual Signal Conditioners K-System | RUS | 3736 KB | |
Instruction manuals | |||
Инструкции | BUL | 135 KB | |
Návod k poużití | CZE | 130 KB | |
Instruktions manual | DAN | 129 KB | |
Instruction manual | ENG | 134 KB | |
Kasutusjuhend | EST | 125 KB | |
Käyttöohje | FIN | 125 KB | |
Manuel d'instructions | FRA | 131 KB | |
Betriebsanleitung | GER | 135 KB | |
Οδηγίες χρήσης | GRE | 138 KB | |
Handleiding | HOL | 129 KB | |
Instruction manual / Betriebsanleitung | HRV | 129 KB | |
Használati útmutató | HUN | 131 KB | |
Manuale di istruzioni | ITA | 129 KB | |
Lietošanas pamācība | LAV | 129 KB | |
Instrukciju vadovas | LIT | 129 KB | |
Instrukcja obsługi | POL | 131 KB | |
Manual de instruções | POR | 129 KB | |
Manual de utilizare | RON | 129 KB | |
Návod na poużitie | SLK | 129 KB | |
Navodila za uporabo | SLV | 127 KB | |
Manual de instrucciones | SPA | 130 KB | |
Manual | SWE | 127 KB |
CAD | File Type | File Size | |
---|---|---|---|
CAD Portal / CAD Portal | LINK | --- | |
Dimension drawing 2-D (DXF) / Abmessungszeichnung 2-D (DXF) | ZIP | 458 KB | |
Dimension drawing 3-D in IGS format / Abmessungszeichnung 3-D im IGS-Format | IGS | 217 KB | |
Dimension drawing 3-D in STP format / Abmessungszeichnung 3-D im STP-Format | STP | 179 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of conformity / EU-Konformitätserklärung | DOC-2550A | 84 KB | |
Certificates | |||
Canada UL cUL | E106378 cUL (QUZW7) | LINK | --- |
Europe Pepperl+Fuchs ATEX Category 3 G | PF 15 CERT 3932 X | 238 KB | |
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378 | CoC 20170828 - E106378 RepRef 20170825 | 401 KB | |
USA UL | E106378 UL (QUZW) | LINK | --- |
Worldwide TUV Rheinland Functional Safety Certificate | 968/FSP 1255.00/16 EN | 678 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
This signal conditioner provides the galvanic isolation between field circuits and control circuits.
The device is a relay module that is suitable for safely switching applications of a load circuit. The device isolates load circuits up to 230 V and the 24 V control circuit.
The energized to safe (ETS) function is permitted for SIL 3 applications.
For testing of the relays, test terminals can be used. The test mode will be indicated by a LED according to NAMUR NE44.
Pepperl+Fuchs is setting a new level of reliability with newly developed safety relays. With multi-redundant switching contacts, the interface module from the tried-and-tested K-System provides reliable and safety-related activation and deactivation for applications in accordance with IEC61508 up to SIL 3.