Relay Module KFD2-RSH-1.2D.FL3

KFD2-RSH-1.2D.FL3
  • 1-channel signal conditioner
  • 24 V DC supply
  • Logic input 19 V DC ... 26.4 V DC
  • Recommended connectable voltage 50 V AC ... 230 V AC, 60 V DC ... 110 V DC
  • Relay contact output for de-energized to safe function
  • Line fault transparency (LFT)
  • Diagnostic function
  • Up to SIL 3 acc. to IEC 61508
  • Up to PL e acc. to EN/ISO 13849

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of KFD2-RSH-1.2D.FL3

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage19 ... 26.4 V DC
Input current35 mA at 24 V DC , max. 44 mA at 19 V DC , with enabled internal fault detection
Power consumption< 1.7 W , includes the power consumption of the digital input , see derating curves
Input
Connection sidecontrol side
Connectionterminals 7+, 8-
Pulse/Pause ratiomin. 150 ms / min. 150 ms with disabled internal fault detection
min. 1 s / min. 1 s with enabled internal fault detection
Test pulse lengthmax. 2 ms from DO card
Signal level0-signal: -5 ... 5 V DC
1-signal: 19 ... 26.4 V DC
Rated current0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card)
1-signal: ≥ 36 mA (minimum load current DO card)
Inrush current< 200 mA after 100 µs
Output
Connection sidefield side
Connectionexternal voltage : terminals 4+, 5+, 2-
load : terminals 6, 3
Connectable voltage50 ... 230 V AC
60 ... 110 V DC
Power dissipation< 3.3 W at 5 A , see derating curves
Contact loading253 V AC/5 A/cos φ 0.7; 30 V DC/5 A resistive load , see derating curves
Minimum switch current10 mA
Mechanical life5 x 106 switching cycles
Line fault detectionlow voltage < 35 V AC
undercurrent: 10 mA AC; overcurrent: 5.5 A AC (relay energized)
breakage: 48 kΩ; short-circuit: 29 Ω (load, relay de-energized)
Fuse rating2.5 A (scope of delivery)
max. 5 AT, recommended maximum utilization of the fuse: 80 %
Fault indication output
Connectionterminals 10, 11
Contact loading30 V DC/ 0.5 A resistive load
Reaction time< 2 s
Mechanical life105 switching cycles
Transfer characteristics
Switching frequency< 3 Hz with disabled internal fault detection
< 0.5 Hz with enabled internal fault detection
Galvanic isolation
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Input/fault indication outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 30 Veff
Output/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Machinery Directive
Directive 2006/42/ECEN 62061:2005+AC:2010+A1:2013+A2:2015 , EN/ISO 13849-1:2015
Conformity
Electromagnetic compatibilityNE 21:2012 , EN 61326-3-2:2008 , EN 61326-3-1:2008
Degree of protectionIEC 60529:2013
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Observe the temperature range limited by derating, see section derating.
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 142 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: KFD2-RSH-1.2D.FL3

ManualsLanguageFile TypeFile Size
Manual Signal Conditioners K-SystemENGPDF694 KB
Original Instructions/Functional Safety ManualENGPDF523 KB
Handbuch Signaltrenner K-SystemGERPDF698 KB
Originalbetriebsanleitung/Handbuch Funktionale SicherheitGERPDF529 KB
Manual Signal Conditioners K-SystemRUSPDF3736 KB
Instruction manuals
ИнструкцииBULPDF0 KB
Návod k poużitíCZEPDF129 KB
Instruktions manualDANPDF128 KB
Instruction manualENGPDF133 KB
KasutusjuhendESTPDF125 KB
KäyttöohjeFINPDF124 KB
Manuel d'instructionsFRAPDF130 KB
BetriebsanleitungGERPDF135 KB
Οδηγίες χρήσηςGREPDF137 KB
HandleidingHOLPDF128 KB
Instruction manual / BetriebsanleitungHRVPDF127 KB
Használati útmutatóHUNPDF130 KB
Manuale di istruzioniITAPDF128 KB
Lietošanas pamācībaLAVPDF128 KB
Instrukciju vadovasLITPDF128 KB
Instrukcja obsługiPOLPDF130 KB
Manual de instruçõesPORPDF129 KB
Manual de utilizareRONPDF128 KB
Návod na poużitieSLKPDF128 KB
Navodila za uporaboSLVPDF126 KB
Manual de instruccionesSPAPDF129 KB
ManualSWEPDF126 KB

Approvals+Certificates: KFD2-RSH-1.2D.FL3

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-3878PDF80 KB
Certificates
Worldwide TUV Rheinland Functional Safety Certificate968/FSP 1538.00/17PDF678 KB
K-System Safety Relays

Triple Protection

Pepperl+Fuchs is setting a new level of reliability with newly developed safety relays. With multi-redundant switching contacts, the interface module from the tried-and-tested K-System provides reliable and safety-related activation and deactivation for applications in accordance with IEC61508 up to SIL 3.