Serviceline Industrial Sensors
Serviceline Explosion Protection

RTD Converter LB5101A

LB5101A
  • 1-channel
  • Input Ex ia
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Converter for 2-, 3- and 4-wire Pt100, slide wire sensors
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Permanently self-monitoring
  • Module can be exchanged under voltage

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  LB5101A

Slots
Occupied slots1
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies LB9***
Power dissipation0.4 W
Power consumption0.4 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
temperature input
Number of channels1
Suitable field devices
Field deviceresistance thermometer
Field device [3]slide-wire sensors
Field device interface
Connection2-wire sensor
Connection [2]3-wire sensor
Connection [3]4-wire sensor
Connection2-wire connection: 5, 6
3-wire connection: 1, 5, 6
4-wire connection: 1, 2, 5, 6
Measurement range10 ... 400 Ω (500 Ω incl. line resistance)
Slide-wire sensor10 ... 400 Ω
Measuring current200 µA
Smallest span20 Ω for 0.1 % accuracy
Linearity error0.1 %
Conversion timemax. 20 ms without LFD max. 150 ms with LFD
Lead resistancemax. 50 Ω per strand
Line fault detectioncan be switched on/off for each channel via configuration tool
Short-circuit< 10 Ω
Open-circuit> 1 kΩ
Transfer characteristics
Deviation
Influence of ambient temperaturemax. 0,1 %/10 K
Indicators/settings
LED indicationPower LED (P) green: supply
Status LED (1) red: line fault
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-56
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 when mounted on backplane
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 90 g
Dimensions16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
EU-Type Examination CertificatePTB 03 ATEX 2042
MarkingEx-Hexagon II (1) G [Ex ia] IIC
Ex-Hexagon II (1) D [Ex ia] IIIC
Input
Voltage2.7 V
Current43 mA
Power93 mW (trapezoid characteristic curve)
CertificatePF 08 CERT 1234 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Galvanic isolation
Input/power supply, internal bussafe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2009
EN 60079-11:2007
EN 60079-15:2010
EN 61241-11:2006
International approvals
ATEX approvalPTB 03 ATEX 2042
UL approvalE106378
Control drawing116-0322
IECEx approvalBVS 09.0037X
Approved forEx nA [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
Marine approval
Lloyd Register15/20021
DNV GL MarineTAA0000034
Bureau Veritas Marine22449/B0 BV
General information
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Documents: LB5101A

ManualsLanguageFile TypeFile Size
Manual LB HardwareENGPDF6465 KB
Handbuch LB-HardwareGERPDF3892 KB
Instruction manuals
ИнструкцииBULPDF0 KB
Návod k poużitíCZEPDF0 KB
Instruktions manualDANPDF140 KB
Instruction manualENGPDF65 KB
KasutusjuhendESTPDF135 KB
KäyttöohjeFINPDF135 KB
Manuel d'instructionsFRAPDF82 KB
BetriebsanleitungGERPDF68 KB
Οδηγίες χρήσηςGREPDF151 KB
HandleidingHOLPDF140 KB
Instruction manual / BetriebsanleitungHRVPDF138 KB
Használati útmutatóHUNPDF0 KB
Manuale di istruzioniITAPDF79 KB
Lietošanas pamācībaLAVPDF139 KB
Instrukciju vadovasLITPDF140 KB
Instrukcja obsługiPOLPDF142 KB
Manual de instruçõesPORPDF141 KB
Manual de utilizareRONPDF140 KB
Návod na poużitieSLKPDF141 KB
Navodila za uporaboSLVPDF138 KB
Manual de instruccionesSPAPDF80 KB
ManualSWEPDF138 KB

Approvals+Certificates: LB5101A

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1066CPDF236 KB
Certificates
American Bureau of Shipping (ABS) Marine15-HG1450280-PDAPDF1468 KB
Brasil TUV Rheinland BrazilTÜV13.1128XPDF938 KB
Bureau Veritas (Maritime) Marine22449/B0 BVPDF287 KB
Canada UL cULE106378 cUL (QUZW7)LINK---
Canada USA UL Certificate of Compliance cULusCoC 20140904 - E106378 RepRef 20010212PDF427 KB
DEKRA EXAM IECEx Certificate of ConformityIECEx BVS 09.0037XLINK---
DNV GL MarineTAA0000034PDF90 KB
EAC NANIO "CCVE" EAC TP TC 012/2011RU C-DE.AA87.B.01017PDF5859 KB
Europe PTB II (2) D II (1D) I (M1) I (M2) II (1) D II (2) GPTB 03 ATEX 2042XPDF1651 KB
Europe Pepperl+Fuchs ATEX Category 3 G Certificate of ConformityPF 08 CERT 1234 XPDF1503 KB
India PESO (India) CCOEA/P/HQ/MH/104/4730 (P383318)PDF728 KB
Lloyd's Register Marine15/20021PDF2013 KB
USA ULE106378 UL (QUZW)LINK---

Function: LB5101A

The RTD converter accepts 2-, 3-, 4-wire RTD signals (Pt100) from the hazardous area.

Open and short-circuit line faults are detected.

The intrinsically safe input is galvanically isolated from the bus and the power supply.