Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Slots | ||
---|---|---|
Occupied slots | 2 | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
Power dissipation | 2.35 W | |
Power consumption | 2.35 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Digital output | ||
Number of channels | 8 | |
Suitable field devices | ||
Field device | Solenoid Valve | |
Field device [2] | audible alarm | |
Field device [3] | visual alarm | |
Connection | channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-; channel V: 9+, 10-; channel VI: 11+, 12-; channel VII: 13+, 14-; channel VIII: 15+, 16- | |
Current limit | 8 mA | |
Open loop voltage | 20 V | |
Line fault detection | can be switched on/off for each channel via configuration tool | |
Test current | 0.33 mA | |
Short-circuit | < 300 Ω | |
Open-circuit | > 50 kΩ | |
Response time | 20 ms (depending on bus cycle time) | |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
Indicators/settings | ||
LED indication | LED green: supply LED red: line fault , communication error red flashing |
|
Coding | optional mechanical coding via front socket | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Environmental test | EN 60068-2-14 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Damaging gas | EN 60068-2-42 | |
Relative humidity | EN 60068-2-56 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
|
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 when mounted on backplane | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) |
|
Mass | approx. 160 g | |
Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 03 ATEX 2042 X | |
Marking | ![]() ![]() |
|
Output | ||
Voltage | 28 V | |
Current | 13.5 mA | |
Power | 376 mW (characteristic curve rectangular type) | |
Certificate | PF 08 CERT 1234 X | |
Marking | ![]() |
|
Galvanic isolation | ||
Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 |
|
International approvals | ||
ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 X |
|
IECEx approval | BVS 09.0037X | |
Approved for | Ex nA [ib Gb] IIC T4 Gc [Ex ib Db] IIIC |
|
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV | |
General information | ||
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. |
|
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Manuals | Language | File Type | File Size |
---|---|---|---|
Functional Safety Manual | ENG | 974 KB | |
Manual | ENG | 3636 KB | |
Handbuch | GER | 3662 KB | |
Handbuch Funktionale Sicherheit | GER | 978 KB | |
Instruction manuals | |||
Инструкции | BUL | 144 KB | |
Návod k poużití | CZE | 139 KB | |
Instruktions manual | DAN | 139 KB | |
Instruction manual | ENG | 64 KB | |
Kasutusjuhend | EST | 134 KB | |
Käyttöohje | FIN | 0 KB | |
Manuel d'instructions | FRA | 81 KB | |
Betriebsanleitung | GER | 67 KB | |
Οδηγίες χρήσης | GRE | 150 KB | |
Handleiding | HOL | 138 KB | |
Instruction manual / Betriebsanleitung | HRV | 137 KB | |
Használati útmutató | HUN | 141 KB | |
Manuale di istruzioni | ITA | 78 KB | |
Lietošanas pamācība | LAV | 138 KB | |
Instrukciju vadovas | LIT | 0 KB | |
Instrukcja obsługi | POL | 142 KB | |
Manual de instruções | POR | 0 KB | |
Manual de utilizare | RON | 139 KB | |
Návod na poużitie | SLK | 140 KB | |
Navodila za uporabo | SLV | 137 KB | |
Manual de instrucciones | SPA | 80 KB | |
Manual | SWE | 0 KB | |
Product information | |||
Product information | ENG | 299 KB | |
Produktinformation | GER | 300 KB |
EPLAN | File Type | File Size | |
---|---|---|---|
EPLAN Data Portal / EPLAN Data Portal | LINK | --- | |
EPLAN macro P+F.LB6108A / EPLAN-Makro P+F.LB6108A | EDZ | 177 KB | |
ePLAN-Makros LB-System / ePLAN-Makros LB-System | ZIP | 65808 KB |
Statements of compliance | Certificate No. | File Type | File Size |
---|---|---|---|
EU-Declaration of conformity / EU-Konformitätserklärung | DOC-1063B | 236 KB | |
Certificates | |||
DEKRA EXAM IECEx Certificate of Conformity | IECEx BVS 09.0037X | LINK | --- |
EAC NANIO "CCVE" EAC TP TC 012/2011 | RU C-DE.AA87.B.01017 | 5859 KB | |
Europe PTB II (2) D II (1D) I (M1) I (M2) II (1) D II (2) G | PTB 03 ATEX 2042X | 1651 KB | |
Europe Pepperl+Fuchs ATEX Category 3 G Certificate of Conformity | PF 08 CERT 1234 X | 1503 KB | |
India PESO (India) CCOE | A/P/HQ/MH/104/4730 (P383318) | 728 KB | |
Lloyd's Register Marine | LR2003616TA-02 | 557 KB | |
Worldwide Pepperl+Fuchs | CERT-4552 | 303 KB |
The device features 8 independent channels.
The device can be used to drive low power solenoids, sounders, or LEDs.
Open and short-circuit line faults are detected.
The outputs are galvanically isolated from the bus and the power supply.
The outputs can be switched off via a contact. This can be used for bus-independent safety applications.