Digital Output with Shutdown Input LB6116E

LB6116E
  • 2-channel
  • Outputs Ex ia
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Line fault detection switched on and off
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog
  • Output with bus-independent safety shutdown
  • Module can be exchanged under voltage (hot swap)

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of LB6116E

Slots
Occupied slots1
Supply
Connectionbackplane bus
Rated voltageUse only in connection with the power supplies LB9***
Power dissipation1.95 W
Power consumption2.9 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Digital output
Number of channels2
Suitable field devices
Field deviceSolenoid Valve
Field device [2]audible alarm
Field device [3]visual alarm
Connectionchannel I: 1+, 4/5/6/8-; channel II: 7+, 4/5/6/8-
Current limit40 mA both channels parallel 80 mA
Internal resistor258 Ω , both channels parallel 129 Ω
Open loop voltage23 V , both channels parallel 23 V
Line fault detectioncan be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms)
Short-circuit< 50 Ω
Open-circuit> 10 kΩ
Response time10 ms (depending on bus cycle time)
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Indicators/settings
LED indicationPower LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1, 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1)
Mode LED (M) white: Parallel operation of outputs
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-56
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 when mounted on backplane
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 150 g
Dimensions16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
EU-Type Examination CertificateEXA 16 ATEX 0025X
MarkingEx-Hexagon II 3(1) G Ex nA [ia Ga] IIC T4 Gc
Ex-Hexagon II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
Output
Voltage24.2 V
Current108 mA
Power654 mW
Internal capacitance12 nF
Internal inductance0 mH
Output (both channels parallel)
Voltage24.2 V
Current216 mA
Power1307 mW
Internal capacitance24 nF
Internal inductance0 mH
Galvanic isolation
Output/power supply, internal bussafe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2009
EN 60079-11:2007
EN 60079-15:2010
EN 61241-11:2006
International approvals
ATEX approvalEXA 16 ATEX 0025X
General information
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Documents: LB6116E

ManualsLanguageFile TypeFile Size
Functional Safety ManualENGPDF974 KB
Manual LB HardwareENGPDF3826 KB
Handbuch Funktionale SicherheitGERPDF978 KB
Handbuch LB-HardwareGERPDF3830 KB
Instruction manuals
ИнструкцииBULPDF0 KB
Návod k poużitíCZEPDF141 KB
Instruktions manualDANPDF140 KB
Instruction manualENGPDF148 KB
KasutusjuhendESTPDF135 KB
KäyttöohjeFINPDF135 KB
Manuel d'instructionsFRAPDF149 KB
BetriebsanleitungGERPDF149 KB
Οδηγίες χρήσηςGREPDF0 KB
HandleidingHOLPDF141 KB
Instruction manual / BetriebsanleitungHRVPDF140 KB
Használati útmutatóHUNPDF0 KB
Manuale di istruzioniITAPDF146 KB
Lietošanas pamācībaLAVPDF139 KB
Instrukciju vadovasLITPDF140 KB
Instrukcja obsługiPOLPDF144 KB
Manual de instruçõesPORPDF143 KB
Manual de utilizareRONPDF141 KB
Návod na poużitieSLKPDF142 KB
Navodila za uporaboSLVPDF138 KB
Manual de instruccionesSPAPDF147 KB
ManualSWEPDF138 KB
Product information
Product informationENGPDF189 KB
ProduktinformationGERPDF243 KB

Approvals+Certificates: LB6116E

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of Conformity / EU-KonformitätserklärungDOC-2602APDF235 KB
Certificates
China NEPSIGYJ 18.1109XPDF4865 KB
EAC NANIO "CCVE" EAC TP TC 012/2011RU C-DE.AA87.B.01017PDF5859 KB
EXA Ex i and Ex nIECEx EXA 16.0010XLINK---
Europe EXA ATEX Category (1) D ATEX Category 3 GEXA 16 ATEX 0025XPDF366 KB
USA Canada, USA UL Certificate of Compliance cULusCoC 20150604 - E106378 RepRef 20140227PDF570 KB
Control drawings
Control drawing UL, CUL / Control drawing UL, cUL   PDF320 KB