Serviceline Industrial Sensors
Serviceline Explosion Protection

Gateway for PROFINET LB8122A.1.EL

LB8122A.1.EL
  • Interface between the I/O modules and the PCS/PLC
  • Mounting in Zone 2, Class I/Div.2 or in the safe area
  • Non-volatile memory for configuration and parameter settings
  • Communication via PROFINET
  • HART communication via PROFINET and HART I/P

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  LB8122A.1.EL

Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies LB9***
Nominal voltage12 V DC ,
Power dissipation3.65 W
Power consumption3.65 W
Fieldbus interface
Fieldbus typePROFINET
Ethernet Interface
Connection typeRJ-45 , via front connector
Transfer rate10BASE-T, 100BASE-TX 100 MBit/s
Station connectiondirectly to PCS or PLC or via hubs or switches
Cable typeSFTP in accordance with ISO/IEC 11801 for Cat 5e or better
Bus lengthmax. 100 m Per link
AddressingDHCP, via controller (DCP) or fixed IP address
Ethernet addressIP V4 address (preset: DHCP on, changeable via display)
Supported I/O modulesLB1x01*…LB1x03*, LB1x08*, LB1x09*, LB2x01*…LB2x17*, LB3x01*…LB3x06*, LB4x01*, LB4x02*, LB4x04*…LB4x06*, LB5x01*, LB5x02*, LB5x04*…LB5x06*, LB6x01*, LB6x05*, LB6x06*, LB6x08*, LB6x10*…LB6x17*
HART communicationvia PROFINET and HART I/P
Internal bus
Connectionbackplane bus
Galvanic isolation
Ethernet/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 35 Veff or 50 V DC
RS 485 interface/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 35 Veff or 50 V DC
Insulation voltage1500 V AC acc. to IEEE 802.3u
Electrical isolation
Power supply, internal bus/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 30 V DC
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Conformity
Degree of protectionIEC 60529
Fieldbus standardIEEE 802.3
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-56
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , mounted on backplane
Connectionvia backplane
Massapprox. 150 g
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
CertificateDEMKO 16 ATEX 1780 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013
EN 60079-15:2010

International approvals
ATEX approvalDEMKO 16 ATEX 1780 X
IECEx approvalIECEx UL 16.0141 X
Approved forEx nA IIC T4 Gc
General information
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity.
For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Documents: LB8122A.1.EL

ManualsLanguageFile TypeFile Size
Configuration instructions STEP 7ENGPDF4210 KB
Configuration instructions TIA PortalENGPDF4521 KB
ManualENGPDF1821 KB
Manual LB HardwareENGPDF6465 KB
Software ManualENGPDF3923 KB
Software Release Notes LB8122A.1.ELENGPDF348 KB
CFC für STEP 7GERPDF1908 KB
Handbuch LB-HardwareGERPDF3892 KB
Konfigurationsanleitung STEP 7GERPDF4229 KB
Konfigurationsanleitung TIA PortalGERPDF4538 KB
Software-HandbuchGERPDF4022 KB
Instruction manuals
ИнструкцииBULPDF152 KB
Návod k poużitíCZEPDF146 KB
Instruktions manualDANPDF145 KB
Instruction manualENGPDF152 KB
KasutusjuhendESTPDF141 KB
KäyttöohjeFINPDF141 KB
Manuel d'instructionsFRAPDF149 KB
BetriebsanleitungGERPDF154 KB
Οδηγίες χρήσηςGREPDF156 KB
HandleidingHOLPDF147 KB
Instruction manual / BetriebsanleitungHRVPDF145 KB
Használati útmutatóHUNPDF148 KB
Manuale di istruzioniITAPDF147 KB
Lietošanas pamācībaLAVPDF144 KB
Instrukciju vadovasLITPDF145 KB
Instrukcja obsługiPOLPDF149 KB
Manual de instruçõesPORPDF148 KB
Manual de utilizareRONPDF146 KB
Návod na poużitieSLKPDF147 KB
Navodila za uporaboSLVPDF144 KB
Manual de instruccionesSPAPDF148 KB
ManualSWEPDF143 KB
Product information
Software Product Note Remote I/O DTM / Softwareproduktschein Remote I/O DTMALLPDF256 KB

CAD+CAE: LB8122A.1.EL

CADFile TypeFile Size
3-D model in IGS format / 3-D-Modell im IGS-FormatIGS6076 KB
3-D model in STP format / 3-D-Modell im STP-FormatSTP1977 KB

Approvals+Certificates: LB8122A.1.EL

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of Conformity / EU-KonformitätserklärungDOC-4202PDF415 KB
Certificates
Canada, USA UL cULus Hazardous LocationCoC 20170105 - E106378 RepRef 20161202PDF403 KB
EU DEMKO ATEX Category 3 GDEMKO 16 ATEX 1780XPDF516 KB
Europe Pepperl+Fuchs II 3 GPF 16 CERT 4057XPDF289 KB
Worldwide UL IECEx nAIECEx UL 16.0141XLINK---

Software: LB8122A.1.EL

DriversRelease InfoFile TypeFile Size
CFC Device Driver Blocks for SIMATIC PCS 7 / CFC Device Driver Blocks für SIMATIC PCS 7ZIP10767 KB
GSD file / GSD-DateiZIP276 KB
Device type managers
DTM / DTMLBFB HART IPZIP9478 KB
PROFINET Gateway

The new, Zone 2, Class I/Div. 2 certified remote I/O PROFINET gateway from Pepperl+Fuchs opens the door for Industry 4.0 applications in process industries.