Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

HART Transmitter Power Supply, Input Isolator FB3305B2

FB3305B2
  • 4-channel
  • Inputs with plug-in Ex e terminals
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Power supply for 2-wire transmitters with 4 mA ... 20 mA
  • Supply circuit 15 V (20 mA)
  • Input from active signals of 4-wire transmitters
  • HART communication via field bus or service bus
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Permanently self-monitoring

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of FB3305B2

Slots
Occupied slots2
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies FB92**
Power dissipation1.5 W
Power consumption2.7 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Analog input
Number of channels4
Suitable field devices
Field devicepressure converter
Field device [2]flow converter
Field device [3]level converter
Field device [4]Temperature Converter
Field device interface
Connection2-wire transmitter
Connection [2]3-wire transmitter
Connection [3]4-wire transmitter
Connection2-wire transmitter (HART): Supply circuit: channel I 1+, 2-, channel II 5+, 6-, channel III 9+, 10-, channel IV 13+, 14- 3-wire transmitter: Supply circuit: channel I 1+, 4-, channel II 5+, 8-, channel III 9+, 12-, channel IV 13+, 16- Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16- 4-wire transmitter (powered externally): Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-
Transmitter supply voltagemin. 15 V at 20 mA ; 21.5 V at 4 mA
Input resistance15 Ω
Conversion timemax. 100 ms
Line fault detectioncan be switched on/off for each channel via configuration tool , configurable via configuration tool
Short-circuitfactory setting: > 22 mA configurable between 0 ... 26 mA
Open-circuitfactory setting: < 1 mA configurable between 0 ... 26 mA
HART communicationyes
HART secondary variableno
Transfer characteristics
Deviation
After calibration0.1 % of the signal range at 20 °C (68 °F)
Influence of ambient temperature0.1 %/10 K of the signal range
Resolution12 Bit (0 ... 26 mA)
Refresh time100 ms
Indicators/settings
LED indicationPower LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1-4) red: line fault (lead breakage or short circuit)
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2006
Conformity
Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2000
Environmental testEN 60068-2-14:2009
Shock resistanceEN 60068-2-27:2009
Vibration resistanceEN 60068-2-6:2008
Damaging gasEN 60068-2-42:2003
Relative humidityEN 60068-2-78:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
ConnectionEx e spring terminal with protective cover
Massapprox. 750 g
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
EU-Type Examination CertificateBVS 11 ATEX E 093 X
MarkingEx-Hexagon II 2 G Ex db eb IIC T4
Galvanic isolation
Input/power supply, internal bussafe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2009
EN 60079-1:2007
EN 60079-7:2007
International approvals
ATEX approvalBVS 11 ATEX E 093X
INMETROBrazil: TÜV 14.1599X
EAC approvalRussia: RU C-IT.MIII06.B.00129
Marine approval
Lloyd Register15/20021
American Bureau of ShippingT1450280/UN
Bureau Veritas Marine22449/B0 BV
General information
System informationThe module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Documents: FB3305B2

ManualsLanguageFile TypeFile Size
Manual - FB-Remote-I/O-SystemENGPDF5670 KB
Handbuch - FB-Remote-I/O-SystemGERPDF1453 KB
Instructions, short instructions, safety information
ИнструкцииBULPDF144 KB
Návod k poużitíCZEPDF136 KB
Instruktions manualDANPDF135 KB
Instruction manualENGPDF61 KB
KasutusjuhendESTPDF133 KB
KäyttöohjeFINPDF131 KB
Manuel d'instructionsFRAPDF78 KB
BetriebsanleitungGERPDF63 KB
Οδηγίες χρήσηςGREPDF148 KB
HandleidingHOLPDF138 KB
Instruction manual / BetriebsanleitungHRVPDF136 KB
Használati útmutatóHUNPDF137 KB
Manuale di istruzioniITAPDF76 KB
Lietošanas pamācībaLAVPDF136 KB
Instrukciju vadovasLITPDF138 KB
Instrukcja obsługiPOLPDF139 KB
Manual de instruçõesPORPDF138 KB
Manual de utilizareRONPDF137 KB
Návod na poużitieSLKPDF137 KB
Navodila za uporaboSLVPDF134 KB
Manual de instruccionesSPAPDF78 KB
ManualSWEPDF133 KB

CAD+CAE: FB3305B2

EPLANFile TypeFile Size
EPLAN Data Portal / EPLAN Data PortalLINK---

Approvals+Certificates: FB3305B2

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1046BPDF233 KB
Certificates
Bureau Veritas (Maritime) Marine22449/B0 BVPDF287 KB
Europe DEKRA EXAMBVS 11 ATEX E 093XPDF618 KB
Lloyd's Register Marine15/20021PDF2013 KB

Associated Products: FB3305B2

Accessories
Standard enclosure for FB-System, Max. 5 slots for I/O modules, For FOUNDATION Fieldbus H1, Impact resistance enclosure, IP66/NEMA 4X, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 24 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 24 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Electropolished enclosure, IP66/NEMA 4X, Housing: stainless steel 1.4404 / AISI 316Lpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Redundancy (field bus and power supply), Housing: stainless steel 1.4404 / AISI 316Lpa