Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

HART Transmitter Power Supply, Input Isolator FB3202B1

FB3202B1
  • 1-channel
  • Input Ex ia
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Power supply for 2-wire transmitters with 4 mA ... 20 mA
  • HART communication via field bus or service bus
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD) and Live Zero monitoring
  • Permanently self-monitoring
  • Supply circuit 15 V (20 mA)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  FB3202B1

Slots
Occupied slots1
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies FB92**
Power dissipation0.75 W
Power consumption1.1 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Analog input
Number of channels1
Suitable field devices
Field devicepressure converter
Field device [2]flow converter
Field device [3]level converter
Field device [4]Temperature Converter
Field device interface
Connection2-wire transmitter
Connection2-wire transmitter (HART):
supply circuit: 2/3+, 4/5-
Transmitter supply voltagemin. 15 V at 20 mA ; 21.5 V at 4 mA
Input resistance15 Ω (terminals 5, 6)

236 Ω (terminals 1, 6) HART
Line fault detectioncan be switched on/off for each channel via configuration tool , configurable via configuration tool
Short-circuitfactory setting: > 22 mA configurable between 0 ... 26 mA
Open-circuitfactory setting: < 1 mA configurable between 0 ... 26 mA
HART communicationyes
HART secondary variableyes
Transfer characteristics
Deviation
After calibration0.1 % of the signal range at 20 °C (68 °F)
Influence of ambient temperature0.1 %/10 K of the signal range
Resolution12 Bit (0 ... 26 mA)
Refresh time100 ms
Indicators/settings
LED indicationPower LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1) red: line fault (lead breakage or short circuit)
Status LED (2) yellow: Live Zero monitoring
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2006
Conformity
Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2000
Environmental testEN 60068-2-14:2009
Shock resistanceEN 60068-2-27:2009
Vibration resistanceEN 60068-2-6:2008
Damaging gasEN 60068-2-42:2003
Relative humidityEN 60068-2-78:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 350 g
Dimensions28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
EU-Type Examination CertificateBVS 12 ATEX E 015 X
MarkingEx-Hexagon II 2(1) G Ex d [ia Ga] IIC T4 Gb
Ex-Hexagon II (1) D [Ex ia Da] IIIC
Supply
Voltage27 V
Current87 mA
Power575 mW (linear characteristic)
Galvanic isolation
Input/power supply, internal bussafe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2009
EN 60079-1:2007
EN 60079-11:2007
EN 60079-26:2007
International approvals
ATEX approvalBVS 12 ATEX E 015 X
INMETROBrazil: TÜV 14.1595X
Marine approval
Bureau Veritas Marine22449/B0 BV
General information
System informationThe module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Documents: FB3202B1

ManualsLanguageFile TypeFile Size
Manual - FB-Remote-I/O-SystemENGPDF5670 KB
Handbuch - FB-Remote-I/O-SystemGERPDF1453 KB
Instruction manuals
ИнструкцииBULPDF148 KB
Návod k poużitíCZEPDF141 KB
Instruktions manualDANPDF140 KB
Instruction manualENGPDF65 KB
KasutusjuhendESTPDF137 KB
KäyttöohjeFINPDF135 KB
Manuel d'instructionsFRAPDF84 KB
BetriebsanleitungGERPDF67 KB
Οδηγίες χρήσηςGREPDF152 KB
HandleidingHOLPDF0 KB
Instruction manual / BetriebsanleitungHRVPDF140 KB
Használati útmutatóHUNPDF141 KB
Manuale di istruzioniITAPDF81 KB
Lietošanas pamācībaLAVPDF140 KB
Instrukciju vadovasLITPDF142 KB
Instrukcja obsługiPOLPDF0 KB
Manual de instruçõesPORPDF0 KB
Manual de utilizareRONPDF141 KB
Návod na poużitieSLKPDF142 KB
Navodila za uporaboSLVPDF139 KB
Manual de instruccionesSPAPDF83 KB
ManualSWEPDF0 KB

CAD+CAE: FB3202B1

EPLANFile TypeFile Size
EPLAN Data Portal / EPLAN Data PortalLINK---

Approvals+Certificates: FB3202B1

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of conformity / EU-KonformitätserklärungDOC-1045BPDF234 KB
Certificates
Bureau Veritas (Maritime) Marine22449/B0 BVPDF287 KB
Europe DEKRA EXAM ATEX Category 2 (1)BVS 12 ATEX E 015 XPDF3324 KB

Associated Products: FB3202B1

Accessories
Standard enclosure for FB-System, Max. 5 slots for I/O modules, For FOUNDATION Fieldbus H1, Impact resistance enclosure, IP66/NEMA 4X, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 24 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 24 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Electropolished enclosure, IP66/NEMA 4X, Housing: stainless steel 1.4404 / AISI 316Lpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Redundancy (field bus and power supply), Housing: stainless steel 1.4404 / AISI 316Lpa

Function: FB3202B1

The transmitter power supply feeds 2-wire transmitters.

Open-circuit, short-circuit, and Live Zero status are detected.

The intrinsically safe input is galvanically isolated from the bus and the power supply.