Serviceline
Serviceline Industrial Sensors
Serviceline Explosion Protection

HART Transmitter Power Supply, Input Isolator FB3205B3

FB3205B3
  • 4-channel
  • Inputs Ex ia
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Power supply for 2-wire transmitters with 4 mA ... 20 mA
  • Supply circuit 15 V (20 mA)
  • Input from active signals of 4-wire transmitters
  • HART communication via field bus or service bus
  • Simulation mode for service operations (forcing)
  • Line fault detection (LFD)
  • Permanently self-monitoring

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH, also apply to Pepperl+Fuchs AG.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  FB3205B3

Slots
Occupied slots2
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies FB92**
Power dissipation1.5 W
Power consumption2.7 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Analog input
Number of channels4
Suitable field devices
Field devicepressure converter
Field device [2]flow converter
Field device [3]level converter
Field device [4]Temperature Converter
Field device interface
Connection2-wire transmitter
Connection [2]3-wire transmitter
Connection [3]4-wire transmitter
Connection2-wire transmitter (HART): Supply circuit: channel I 1+, 2-, channel II 5+, 6-, channel III 9+, 10-, channel IV 13+, 14- 3-wire transmitter: Supply circuit: channel I 1+, 4-, channel II 5+, 8-, channel III 9+, 12-, channel IV 13+, 16- Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16- 4-wire transmitter (powered externally): Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-
Transmitter supply voltagemin. 15 V at 20 mA ; 21.5 V at 4 mA
Input resistance15 Ω
Conversion timemax. 100 ms
Line fault detectioncan be switched on/off for each channel via configuration tool , configurable via configuration tool
Short-circuitfactory setting: > 22 mA configurable between 0 ... 26 mA
Open-circuitfactory setting: < 1 mA configurable between 0 ... 26 mA
HART communicationyes
HART secondary variableno
Transfer characteristics
Deviation
After calibration0.1 % of the signal range at 20 °C (68 °F)
Influence of ambient temperature0.1 %/10 K of the signal range
Resolution12 Bit (0 ... 26 mA)
Refresh time100 ms
Indicators/settings
LED indicationPower LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1-4) red: line fault (lead breakage or short circuit)
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2006
Conformity
Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2000
Environmental testEN 60068-2-14:2009
Shock resistanceEN 60068-2-27:2009
Vibration resistanceEN 60068-2-6:2008
Damaging gasEN 60068-2-42:2003
Relative humidityEN 60068-2-78:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 955 g
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
EU-Type Examination CertificatePresafe 19 ATEX 14056U
MarkingEx-Hexagon II 2(1)G Ex db eb q [ia Ga] IIC Gb
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
Supply
Voltage27 V
Current90 mA
Power588 mW (linear characteristic)
Input
Voltage0.7 V
Current2.78 mA
Power2 mW (trapezoid characteristic curve)
Internal capacitance242 nF
Internal inductance0 mH
Galvanic isolation
Input/power supply, internal bussafe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013
EN 60079-1:2014
EN 60079-5:2015
EN 60079-7:2015
EN 60079-11:2012
International approvals
ATEX approvalPresafe 19 ATEX 14056U
IECEx approvalIECEx PRE 19.0011U
Approved forEx db eb q [ia Ga] IIC Gb
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
System informationThe module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Documents: FB3205B3

Instruction manualsLanguageFile TypeFile Size
ИнструкцииBULPDF166 KB
Návod k poużitíCZEPDF161 KB
Instruktions manualDANPDF160 KB
Instruction manualENGPDF167 KB
KasutusjuhendESTPDF155 KB
KäyttöohjeFINPDF154 KB
Manuel d'instructionsFRAPDF164 KB
BetriebsanleitungGERPDF168 KB
Οδηγίες χρήσηςGREPDF173 KB
HandleidingHOLPDF162 KB
Instruction manual / BetriebsanleitungHRVPDF160 KB
Használati útmutatóHUNPDF162 KB
Manuale di istruzioniITAPDF163 KB
Lietošanas pamācībaLAVPDF159 KB
Instrukciju vadovasLITPDF160 KB
Instrukcja obsługiPOLPDF163 KB
Manual de instruçõesPORPDF163 KB
Manual de utilizareRONPDF162 KB
Návod na poużitieSLKPDF162 KB
Navodila za uporaboSLVPDF159 KB
Manual de instruccionesSPAPDF164 KB
ManualSWEPDF157 KB

Approvals+Certificates: FB3205B3

Statements of complianceCertificate No.File TypeFile Size
EU-Declaration of Conformity / EU-KonformitätserklärungDOC-4261PDF419 KB
Certificates
Europe Presafe DNV GL II 2(1)G I (M1) ATEX II (1) DPresafe 19 ATEX 14056UPDF257 KB
Presafe DNV GL IECEx Certificate of ConformityIECEx PRE 19.0011ULINK---

Associated Products: FB3205B3

Accessories
Standard enclosure for FB-System, Max. 5 slots for I/O modules, For FOUNDATION Fieldbus H1, Impact resistance enclosure, IP66/NEMA 4X, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 24 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 24 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Electropolished enclosure, IP66/NEMA 4X, Housing: stainless steel 1.4404 / AISI 316Lpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, Installation in Zone 1 and Zone 21, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Housing: polyester , impact resistant, glass fiber reinforcedpa
Standard enclosure for FB-System, Max. 48 slots for I/O modules, For PROFIBUS DP, PROFIBUS DP V1 and MODBUS RTU, Redundancy (field bus and power supply), Housing: stainless steel 1.4404 / AISI 316Lpa